4.2 Control Circuit and External Battery Interface Connections 75 and 100kVA
The following illustrates the wiring connections of the Control Circuits, and Battery Interface
Circuits.
4.2.1 Recommended Wire Size and Tightening Torque UPS Control and Battery
Interface
Minimum Wire Size and Tightening Torque for UPS Control and Battery Interface Circuits
USE MINIMUM 75° C COPPER WIRING
TERMINAL
(TERMINAL #)
75kVA 100kVA
AWG
TIGHTENING
TORQUE
AWG
TIGHTENING
TORQUE
UPS CONTROL CIRCUITS
(1-24)*
14-16 8 in-lbs. 14-16 8 in-lbs.
BATTERY CONTROL
CIRCUITS (3-6)*
14-16 8 in-lbs. 14-16 8 in-lbs.
*Indicates Class 1 wiring methods is to be used.