103
4400 Series Installation and Operation Manual – 64527-008
15 External Layouts/Dimensions/Shipping Weights
TABLE 15.1: DIMENSIONAL DATA
EXTERNAL DIMENSIONS SHIPPING DIMENSIONS
1
Unit Width Depth Height Width Depth Height
15-30 kVA 20.12 in
(511 mm)
37.4 in
(950)
65.06 in
(1653 mm)
43 in
(1092 mm)
49 in
(1245 mm)
72 in
(1829 mm)
50 kVA 32.1 in
(816 mm)
37.2 in
(944 mm)
73.8 in
(1874 mm)
46 in
(1168 mm)
49 in
(1245 mm)
90 in
(2286 mm)
80-100 kVA 32.1 in
(816 mm)
37.2 in
(944 mm)
73.6 in
(1869 mm)
46 in
(1168 mm)
49 in
(1245 mm)
90 in
(2286 mm)
1. Subject to change without notice.
TABLE 15.2: CONDUIT KNOCKOUT DIMENSIONS
CABLE ACCESS OPENING SIZES (15/20/25/30/50/80/100 KVA)
Left/Right Side 6 in (152 mm) x 9 in (229 mm)
Top 4.75 in (121 mm) x 16.5 in (419 mm)
Bottom 4.75 in (121 mm) x 16.5 in (419 mm)
TABLE 15.3: UNIT AND SHIPPING WEIGHTS
Model
Unit Weight
1
Shipping Weight
1,2
Pounds Kilograms Pounds Kilograms
15 kVA 720 327 875 397
15 kVA w/ Int. Batt. 1000 454 1155 525
15 kVA w/ 2 Xfmrs - - - -
20 kVA 720 327 875 397
20 kVA w/ Int. Batt. 1000 454 1155 525
20 kVA w/ 2 Xfmrs - - - -
25 kVA 720 327 875 397
25 kVA w/ Int. Batt. 1000 454 1155 525
25 kVA w/ 2 Xfmrs 1120 508 1275 578
30 kVA 720 327 875 397
30 kVA w/ Int. Batt. 1000 454 1155 525
30 kVA w/ 2 Xfmrs 1115 506 1270 576
50 kVA 1350 612 1505 683
50 kVA w/ Int. Batt. - - - -
50 kVA w/ 2 Xfmrs - - - -
80 kVA 1500 680 1655 751
80 kVA w/ 1 Xfmr - - - -
100kVA 1,650 784 1,770 802
1. Subject to change without notice.
2. Shipping weights include 120 lb. (54.4 kg) for shipping pallet, and 35 lb. (15.9 kg) for shipping rails.