113
4400 Series Installation and Operation Manual – 64527-008
Blk Item Long Description
Short
Description
Units
Permiissions
Remark
User Admin
2 26 Output Current % (C) Current % (C) % R R
2 28 Output Power W % (Total) Power W %
(Total)
% R R
2 36 Output Power Factor Power Factor 0.01 R R
2 39 Rated Power Factor Rated Power
Factor
0.01 R R
2 40 No of Output Line No of Output Line R R
2 41 Rated Line to Line Output Volt-
age
Rated Voltage L-L V R R/W
2 42 Rated Line to Neutral Output
Voltage
Rated Voltage
L-N
V R R/W
2 44 Rated Output Frequency Rated Frequency Hz R R
2 45 Rated Output Power (W) Rated Power (W) W R R
2 46 Rated Output Power (VA) * Rated Power (VA) VA R R
2 47 VOUV Detection Level VOUV DeLevel % R R
2 49 VOOV Detection Level VOOV DeLevel % R R
2 60 Output Voltage Adjustment
(Customer)
Vout Adjustment V R R/W
3 01 Bypass Line to Line Voltage
(AB)
Voltage (AB) V R R
3 02 Bypass Line to Line Voltage
(BC)
Voltage (BC) V R R
3 03 Bypass Line to Line Voltage
(CA)
Voltage (CA) V R R
3 04 Bypass Line to Neutral Voltage
(AN)
Voltage (AN) V R R
3 05 Bypass Line to Neutral Voltage
(BN)
Voltage (BN) V R R
3 06 Bypass Line to Neutral Voltage
(CN)
Voltage (CN) V R R
3 07 Bypass Phase Current (A) Current (A) A R R
3 08 Bypass Phase Current (B) Current (B) A R R
3 09 Bypass Phase Current (C) Current (C) A R R