Blk Item Long Description
Short
Description
Units
Permiissions
Remark
User Admin
3 10 Bypass Frequency Frequency Hz R R 600 for 60.0 Hz, 500 for 50.0 Hz. UPS will send you one
decimal point and format it according to decimal points
3 21 Bypass Voltage % (A) Voltage % (A) % R R
3 22 Bypass Voltage % (B) Voltage % (B) % R R
3 23 Bypass Voltage % (C) Voltage % (C) % R R
3 40 No of Bypass Line No of Bypass
Line
R R
3 41 Rated Line to Line Bypass Volt-
age
Rated Voltage L-L V R R
3 42 Rated Line to Neutral Bypass
Voltage
Rated Voltage
L-N
V R R
3 47 Bypass UV Detection Level VbUV DeLevel % R R
3 49 Bypass OV Detection Level VbOV DeLevel % R R
4 01 DC Bus Total DC Bus Total Vdc - R
4 02 DC Bus Positive DC Bus (+) Vdc - R
4 03 DC Bus Negative DC Bus (-) Vdc - R
5 01 Battery Voltage Battery Voltage Vdc R R
5 02 Battery Current Battery Current A R R
5 04 Battery Backup Time Backup Time Sec R R Counts up elapsed time while on Battery Backup Mode.
Note: this does not display an estimate of total
backup time capacity.
5 05 Battery Capacity Battery Capacity % R R
5 06 Charger Status Charger Status R R 1 – Charging
4 – Equalize
8 – Protective
16 – Discharging
32 – Stopped
All other values show O
5 07 Rated Battery Voltage Rated Voltage Vdc R R
5 08 Rated Battery Discharged Cur-
rent
Rated Dis Current Adc R R
5 11 Equalized Charging* Equal Ch - R 0 – Disable
1 – Enable