Installation Planning Guide for 15-100kVA UPS
Standard System: 208/120V Input, 208/120V Output
Rev. 1.6 Page 2 of 3 4400-IPG-208/120v-208/120V
AC Output (208/120V 3-Phase / 4-Wire)
Rated Output Power
Suggested External
Feeder Breaker
Suggested Minimum Feeder Wire Size
Per Phase / Neutral
Suggested Maximum Feeder Length
For Min. Wire Size in Steel Conduit
kVA PF Amps Amps AWG or kcmil at 75º C Temp. Rating Feet
(1) x 6 AWG / (1) x 2 AWG
(1) x 3 AWG / (1) x 2 AWG
(1) x 2 AWG / (1) x 2 AWG
(1) x 2 AWG / (1) x 2 AWG
(1) x 4/0 / (1) 250 kcmil
80 0.9 222 350 A
(2) x 2/0 AWG – (1) x 400 kcmil /
(2) x 300 kcmil
380
100 0.9 278 450 A
(2) x 3/0 AWG – (1) x 600 kcmil /
(2) x 500 kcmil
380