124
4400 Series Installation and Operation Manual – 64527-008
D.7 – Input Transformer Current for Given Input Voltage
TABLE D.7 – INPUT TRANSFORMER CURRENT FOR GIVEN INPUT VOLTAGE
Input
Voltage
Input Current (Input Currrent + Charging Current) at Full Load (A)
15 kVA 20 kVA 25 kVA 30 kVA 50 kVA 80 kVA
208/120V 42 (46) 55 (60) 69 (74) 83 (88) 139 (148) 222 (238)
220/127V 41 (45) 54 (59) 68 (72) 81 (86) 136 (144) 217 (232)
230/133V 39 (43) 52 (56) 65 (69) 78 (82) 130 (138) 207 (222)
240/139V 37 (41) 50 (54) 62 (66) 75 (79) 124 (132) 199 (213)
380/220V 24 (26) 31 (34) 39 (42) 47 (50) 78 (84) 126 (134)
400/227V 22 (25) 30 (32) 37 (39) 45 (47) 75 (79) 119 (128)
415/240V 22 (24) 29 (31) 36 (38) 43 (46) 72 (77) 115 (123)
480/277V 19 (21) 25 (27) 31 (33A 37 (39) 62 (66) 99 (106)
600/347V 15 (17) 20 (22) 25 (27) 30 (32) 50 (53) 80 (85)
D.8 – Output Transformer Current for Given Output Voltage
TABLE D.8 – OUTPUT TRANSFORMER CURRENT AT GIVEN OUTPUT VOLTAGE
Output
Voltage
Output Current at Full Load (A)
15 kVA 20 kVA 25 kVA 30 kVA 50 kVA 80 kVA
208/120V 42 56 69 83 139 222
220/127V 39 52 66 79 131 210
230/133V 38 50 63 75 126 201
240/139V 36 48 60 72 120 192
380/220V 23 30 38 46 76 122
400/227V 22 29 36 43 72 115
415/240V 21 28 35 42 70 111
480/277V 18 24 30 36 60 96
600/347V 14 19 24 29 48 77