71
4400 Series Installation and Operation Manual – 64527-008
4400 SPECIFICATIONS: 50–100kVA w/ External Battery Backup
50kVA 80kVA 100kVA
Battery Capacity Required at Full Load
(kWB)
49.5 kWB 79.2 kWB 98.9 kWB
Battery Test (Interval per hr) Ye s
Pre-alarm Level (Vdc) 250 Vdc
Battery Protection Internal – Fuse / Ext. – MCCB
Overvoltage Protection Cuto @ 110% Floating Charge
Protection against Batteries Deep
Discharge
Automatically adjust cuto voltage
Eciency DC-AC (%) >92%
BATTERY – INTERNAL (N/A)
ENVIRONMENT
Cooling -Forced Air (cfm) 5 x 452 cfm (max.)
Operating Temperature (°F/°C) 32°F – 104°F (0 °C – 40 °C)
Storage Temperature (°F/°C) 14°F – 122°F (-10 °C – 50 °C)
Operating Humidity (%) 5 – 95% RH
Altitude (ft./m) 3300 ft. (1000 m) w/o derating
Location Indoors in dust and moisture free environment
Heat Rejection at 100% Full Load
(BTU/Hour)
15,034
(Ref. Table 11.10)
24,054
(Ref. Table 11.10)
30,372
(Ref. Table 11.10)
Audible Noise (dBA) ~63dB (‘A’ Scale @ 1m) <70 dB (‘A’ Scale @ 1m)
MECHANICAL
Weight
2
lb/(kg)
with No Transformer
with 1 Transformer
with 2 Transformers
965 lbs. (438 kg)
1370 lbs. (612 kg)
1695 lbs. (612 kg)
1550 lbs. (612 kg)
1735 lbs. (612 kg)
N/A
1650 lbs. (748 kg)
N/A
N/A
Dimensions WxDxH (in/mm) 32.1 in x 37.2 in x 73.8 in (816 mm x 944 mm x 1874 mm)
Shipping Weight
2
lb/(kg)
with No Transformer
with 1 Transformer
with 2 Transformers
1115 lbs. (612 kg)
1520 lbs. (612 kg)
1845 lbs. (612 kg)
1670 lbs. (612 kg)
1855 lbs. (612 kg)
N/A
1,770 lbs. (803 kg)
N/A
N/A
Shipping Dimensions WxDxH (in/mm) 46 in x 48 in x 90 in (1168 mm x 1219 mm x 2286 mm)
Clearance (in/mm)
2
Front – 36 in (900 mm) (per NEC or Local Code) / Top – 16 in (406 mm)
Sides/Back – Zero clearance
Enclosure NEMA 1
Construction Welded Steel Chassis
Color Powder Coat, Dupont O’Brien Black
Emergency Power O (EPO) Yes
Control Panel Touchscreen and LED
MONITORING
Operator Interface (Front Panel) Touchscreen and LED
Dry Contacts Included Yes
RS-232 Interface Yes
Optional – Intelligent Monitoring Yes – RemotEye 4