4400 Series Installation and Operation Manual – 64527-008
12.3 Operator Controls
Bypass/On-Line Switch
Switches the UPS between On-Line and Bypass modes.
Display Reset Switch
Allows the display to be rebooted without powering down the UPS. The display can be reset by pressing the Reset Switch
with a thin probe, such as a paper clip.
󰀨
These units are equipped with a front panel mounted EPO switch.
This safety feature enables quick shutdown of the UPS AC output and battery circuits.
The EPO function is initiated by pressing the red EPO switch. The e󰀨ect of using the EPO switch is the same whether the
UPS is in the AC Input Mode, Battery Backup Mode, or the Bypass Mode.
The following gure shows the UPS condition after application of the EPO switch. See Section 13.4 Restore System
Power after an EPO Shutdown.
FIGURE 12.2: EFFECT OF EPO ACTIVATION
Contactor
AC/DC
Converter
DC/AC
Inverter
4400 UPS
Bypass Thyristor
MCCB
AC Input
3Φ 4W
AC Output
3Φ 4W
Input
Contactor
Output
Contactor
DC/DC
Converter
Ground
Wire
Fuse
Fuse
SYNC
Fuse
TRIPPED
OFF
OFF OFF