216 ACE-tronics G9 ASD Installation and Operation Manual
My Function Frequency Data 5
Program My Function My Function Data
This parameter is used to set the trigger threshold level of the analog signal of
the My Function Frequency Data 5.
The analog signal is selected using the Input Setting number from Table 10 on
pg. 242.
Direct Access Number — F927
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Ye
s
Minimum — 0.00
Maximum — 200.00
Units — %
My Function Time Data 1
Program My Function My Function Data
This parameter is used to set the response delay of the My Function Time
Data 1 terminal.
The applied discrete input signal must be present at the input terminal of the
ASD for the time setting here for a system response.
Discrete terminal input activation that does not equal or exceed this setting will
be ignored.
Direct Access Number — F928
Parameter Type — N
umerical
Factory Default — 0.01
Changeable During Run — Ye
s
Minimum — 0.01
Maximum — 600.00
Units — Seconds
My Function Time Data 2
Program My Function My Function Data
This parameter is used to set the response delay of the My Function Time
Data 2 terminal.
The applied discrete input signal must be present at the input terminal of the
ASD for the time setting here for a system response.
Discrete terminal input activation that does not equal or exceed this setting will
be ignored.
Direct Access Number — F929
Parameter Type — N
umerical
Factory Default — 0.01
Changeable During Run — Ye
s
Minimum — 0.01
Maximum — 600.00
Units — Seconds
My Function Time Data 3
Program My Function My Function Data
This parameter is used to set the response delay of the My Function Time
Data 3 terminal.
The applied discrete input signal must be present at the input terminal of the
ASD for the time setting here for a system response.
Discrete terminal input activation that does not equal or exceed this setting will
be ignored.
Direct Access Number — F930
Parameter Type — N
umerical
Factory Default — 0.01
Changeable During Run — Ye
s
Minimum — 0.01
Maximum — 600.00
Units — Seconds
My Function Time Data 4
Program My Function My Function Data
This parameter is used to set the response delay of the My Function Time
Data 4 terminal.
The applied discrete input signal must be present at the input terminal of the
ASD for the time setting here for a system response.
Discrete terminal input activation that does not equal or exceed this setting will
be ignored.
Direct Access Number — F931
Parameter Type — N
umerical
Factory Default — 0.01
Changeable During Run — Ye
s
Minimum — 0.01
Maximum — 600.00
Units — Seconds
F927 F931