MELSEC-
A
3 SPECIFICATION
3 SPECIFICATION
This chapter provides the specifications of the AJ65VBTCU-68ADVN/ADIN.
3.1 General Specification
Table 3.1 indicates the general specifications of the AJ65VBTCU-68ADVN/ADIN.
Table 3.1 General specification
Item Specification
Usage ambient temperature 0 to 55°C
Storage ambient temperature -20 to 75°C
Usage ambient humidity 10 to 90%RH, no condensation
Storage ambient humidity 10 to 90%RH, no condensation
When there is intermittent vibration
Frequency Acceleration Amplitude Sweep count
10 to 57Hz
0.075mm
(0.0030inch)
57 to 150Hz
9.8m/s
2
When there is continuous vibration
Frequency Acceleration Amplitude
10 to 57Hz
0.035mm
(0.0013inch)
Vibration durability
Conforming to JIS B
3502, IEC 61131-2
57 to 150Hz
4.9m/s
2
10 times in each direction
X, Y, Z (80 minutes)
Shock durability
Conforming to JIS B 3502, IEC61131-2 (147m/s
2
, 3 times each in 3 directions)
Usage environment No corrosive gas
Usage height Less than 2000 m (less than 6562 ft.)
Installation area Within the control board
Over-voltage category *
1
Less than II
Pollution level *
2
Less than 2
*1 Indicates the location where the device is connected from the public cable network to the device structure wiring
area.
Category II applies to the devices to which the power is supplied from a fixed equipment.
Surge withstand voltage for devices with up to 300V of rated voltage is 2500V.
*2 This is an index which indicates the degree of conductive object generation in the environment Pollution level 2 is
when only non-conductive pollution occurs.
A temporary conductivity caused by condensation must be expected occasionally.
*3 Do not operate or store the PLC in the environment where the pressure applied is equal to greater than the
atmospheric pressure at the altitude of 0m.
Doing so may cause a malfunction. Please consult our branch office when the PLC is to be operated under
pressure.