Touch Screen Controller Owner's Manual
93
-EN
Set Energy threshold
1 In [1-(1)], tap [1-(2)]
2 Tap [2-(1)]
3 Tap [3-(1)] and set the pulse constant for each of channels
1 to 8
NOTE
Ensure that the pulse constant matches the output pulse of the pulse
transmission type watt hour meter connected to the Unit.
Channels 1 to 8 correspond to external input terminals DIs 1 to 8.
Enter each pulse constant in either the [pulse/kWh] or [kWh/pulse] field. In
the field in which no pulse constant is entered, the reciprocal of the entered
value is displayed.
Before setting these items, initial settings are required. For details, contact
service personnel.
4 Set data in [4-(1)] and [4-(2)]
NOTE
In Measurement time, set the measurement time for power usage.
For Threshold 1 to Threshold 4, set the power usage in the measurement
time cycle.
A threshold of 0 means that no threshold is set.
Enter thresholds, starting with Threshold 1, in such a way that the threshold
gets larger as the number increases. You cannot skip any number.
If the actual power usage is 250 kWh, Threshold 1 (110 kWh) and
Threshold 2 (210 kWh) are exceeded. Thus, power peak cut controls 1 and
2 are executed.
1
-(1)
1
-(1)
1
-(2)
1
-(2)
3
-(1)
3
-(1)
2
-(1)
2
-(1)
4
-(1)
4
-(1)
4
-(2)
4
-(2)
Threshold 4
Threshold 3
Threshold 2
Threshold 1