17
<Specifications for Wiring>
Use the following materials to connect signal lines and power lines (locally procured)
No Line Type / Wire size / Length
1 For TCC-LINK
2-core shield wire
1.25mm², 1000m max. (total length including
2.00mm², 2000m max. air conditioner area)
2 For RS-485
2-core shield wire
1.25mm², 500m max. (total length)
3
For power
(220 - 240VAC)
H05RN-F or 245IEC57
0.75mm², 50m max.
4 For digital Input / Output connection
2-core wire
0.3mm², 100m max.
5
For power supply
(Between the power unit and central controller)
4-core wire
0.75mm², 20m max.