22
1
ON
OFF
2 3 4 5 6 7 8
DS24
<4> Always OFF
Always set this bit to OFF.
<5> Control group Selection line
OFF: LINE 1
ON: LINE 2
* Set a line number for which the control group selection is used.
Factory default: All OFF
CENTRAL 1:Disables operation start / stop using the remote controller.
CENTRAL 2:Disables operation start / stop, operation mode switching, and temperature setting using the remote
controller.
Switch No.
<1> <2> <3>Central controller operation
Timer OFF ON Timer ON OFF
(1) All ON All OFF OFF OFF OFF
(2) No change All OFF ON OFF OFF
(3)
All indoor units are locally
controllable.
All indoor units CENTRAL 1 OFF ON OFF
(4)
All OFF and all indoor units to
be CENTRAL 1
ON ON OFF
(5) All indoor units CENTRAL 2 OFF OFF ON
(6)
All OFF and all indoor units to
be CENTRAL 2
ON OFF ON
<6> Control group selection enable
OFF: Normal mode
ON: Control group selection
Set this bit to ON when the control group selection is used.
* To use the control group selection, set DS23-<2> to <5> and DS24-<5>
to <6>. For details, see “9. Mode setting for Smart Manager with data
analyzer”.
<7> Buzzer
OFF: With buzzer sound
ON: Without buzzer sound
<8> indication
OFF: Displayed
ON: Not displayed
<1> to <3> Timer input switching
These bits switch operation when the weekly timer has changed.
Use (1) and (2) only in the remote control mode.
When the control group selection is used, “All ON,” “All OFF” and
“all indoor units” mean those within the set group range.
<DS24>