117
Drawing-out port of lead wire
Screw
Screws
Screw
Screw
Wire cover A
Wire cover B
Ferrite core for sensor lead
Card edge spacer
Card edge spacer
Card edge spacer
Ferrite core for fan motor
1. Detachment
1) Perform works of procedure
4
-1.
2) Remove connectors of the lead wire connected to the following connectors of the control
P.C. board.
CN33 : Flap motor (5P, White)
CN34 : Float switch (3P, Red)
CN68 : Drain pump (3P, Blue)
CN100: TC1 sensor (3P, Brown)
CN101: TC2 sensor (2P, Black)
CN102: TCJ sensor (2P, Red)
CN82 : PMV (6P, Blue)
CN333: Fan motor power supply (5P, White)
CN334: Fan motor position detection (5P, White)
NOTE)
Remove the connectors after unlocking the lock of the housing.
3)Remove each lead wire from cord clamps in the electric parts box.
4) Remove the power supply
wiring, remote controlwiring,
and control wiring.
5) Attach the wire cover A and
wire cover B. (Ø4 × 0.31"(8mm,
3 pcs.))
6) Take off 2 screws which fix the
electricparts box and then
remove the electric parts box.
2. Attachment
1) Tighten screws (Ø4 × 0.31"(8mm,
2 pcs.)) fixing the electric parts box.
2) Connect the connectors as
original before being removed
in item 1.
3) Attach the wire cover B.
4) Connect the power supply
wiring, remote control wiring,
and control wiring as before.
5) Attach the wire cover A.
No.
6
Part name
Electric
parts box
Procedure Remarks
NOTE)
Referring to NOTE) (5) in the previous page, connect wires as same as before wiring.