No.
8
9
10
11
12
Item
Recovery control for
cooling oil
(Refrigerant)
Recovery control for
heating refrigerant
(Oil)
Compensation
control for short
intermittent operation
Elimination of
retained heat
Display of filter sign
[
]
(Not provided to the
wireless type)
Separately set type
TCB-AX21UL is
prepared.
Outline of specifications
The indoor unit which is under STOP/Thermo-OFF
status or which operates in [FAN] mode performs the
following controls when it received the cooling oil
(Refrigerant) recovery signal from the outdoor unit.
1) Opens PMV of the indoor unit with a constant
opening degree.
2) Operates the indoor fan for approx. 3 minutes
during recovery control and after finish of control.
The indoor unit which is under STOP/Thermo-OFF
status or which operates in [FAN] mode performs the
following controls when it received the heating refrigerant
(Oil) recovery signal from the outdoor unit.
1) Opens PMV of the indoor unit with a constant
opening degree.
2) Stop the indoor fan.
1) For 3 minutes after start of operation, the operation
is forcedly continued even if the unit enters in
Thermo-OFF condition.
2) However the thermostat is OFF giving prior to
COOL/HEAT selection, ready for operation and
protective control.
1) When the unit stopped from [HEAT] operation, the
indoor fan operates with [L] for approx. 30 seconds.
1) The filter sign is displayed with LC by sending the
filter-reset signal to the remote controller when the
specified time (150H) elapsed as a result of integra-
tion of the operation time of the indoor fan.
2) The integrated timer is cleared when the filter-reset
signal is received from the remote controller.
In this time, if the specified time elapsed, the counted
time is reset and the LC display is deleted.
Remarks
Recovery operation is
usually performed every
2 hours 5 minutes.
The indoor unit which is
under thermo-OFF
(COOL) status or which
operates in [FAN] mode
stops the indoor fan and
displays [
].
Recovery operation is
usually performed every
1 hour.
(When there is even 1
indoor unit which the
thermo unit is off)
Usually the priority is given
to 5 minutes at outdoor
controller side.
[ FILTER] goes on.