EasyManua.ls Logo

Toshiba Carrier MMK-AP0073H2UL - Page 89

Toshiba Carrier MMK-AP0073H2UL
173 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
89
Check code
Location
of
detection
Description System status
Error detection
condition(s)
Check items (locations)
Main
remote
controller
Outdoor 7-segment display
Check code
Sub-code
E31 E31
Symbol O
signifies site of
IPDU error.
I/F IPDU
communication
error
All stop Communication is disrupted
between IPDUs (P.C.
boards) in inverter box.
Check wiring and
connectors involved in
communication between
IPDU-I/F P.C. board for
bad contact or broken wire.
Check for defect in outdoor
P.C. board (I/F, A3-IPDU
or Fan IPDU).
Check for external noise.
F01
Indoor
unit
Indoor TCJ
sensor error
Stop of
corresponding
unit
Sensor resistance is infinity
or zero (open/short circuit).
Check connection of TCJ
sensor connector and
wiring.
Check resistance
characteristics of TCJ
sensor.
Check for defect in indoor
P.C. board.
F02
Indoor
unit
Indoor TC2
sensor error
Stop of
corresponding
unit
Sensor resistance is infinity
or zero (open/short circuit).
Check connection of TC2
sensor connector and
wiring.
Check resistance
characteristics of TC2
sensor.
Check for defect in indoor
P.C. board.
F03
Indoor
unit
Indoor TC1
sensor error
Stop of
corresponding
unit
Sensor resistance is infinity
or zero (open/short circuit).
Check connection of TC1
sensor connector and
wiring.
Check resistance
characteristics of TC1
sensor.
Check for defect in indoor
P.C. board.
F04 F04
I/F TD1 sensor
error
All stop Sensor resistance is infinity
or zero (open/short circuit).
Check connection of TD1
sensor connector.
Check resistance
characteristics of TD1
sensor.
Check for defect in outdoor
P.C. board (I/F).
F05 F05
I/F TD2 sensor
error
All stop Sensor resistance is infinity
or zero (open/short circuit).
Check connection of TD2
sensor connector.
Check resistance
characteristics of TD2
sensor.
Check for defect in outdoor
P.C. board (I/F).
F06 F06
01:
TE1 sensor error
02:
TE2 sensor error
I/F TE1/TE2
sensor error
All stop Sensor resistance is infinity
or zero (open/short circuit).
Check connection of TE1/
TE2 sensor connectors.
Check resistance
characteristics of TE1/TE2
sensors.
Check for defect in outdoor
P.C. board (I/F).
F07 F07
I/F TL sensor error All stop Sensor resistance is infinity
or zero (open/short circuit).
Check connection of TL
sensor connector.
Check resistance
characteristics of TL
sensor.
Check for defect in outdoor
P.C. board (I/F
).
A3-IPDU
Fan
IPDU
O
O
O
O
O
O
O
O
231
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
01
02
03
04
05
06
07
08
09
0A
0B
0C
0D
0E
0F

Related product manuals