EasyManua.ls Logo

Toshiba Carrier MMK-AP0093H2UL - Page 70

Toshiba Carrier MMK-AP0093H2UL
173 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
70
Function to clear error
1. Clearing method from remote controller
~ How to clear error of outdoor unit
In the unit of refrigerant line connected by indoor unit of the remote controller to be operated, the error of
the outdoor unit currently detected is cleared. (Error of the indoor unit is not cleared.)
The service monitor function of the remote controller is utilized.
<Method>
1 Push
CL
+
TEST
buttons simultaneously for 4 seconds or more to change the mode to service
monitor mode.
2 Push
TEMP.
button to set the item code to [ FF ].
3 The display of A part in the following figure is counted as 0005
0004
0003
0002
0001
0000 with 5-seconds interval.
When “
0000 appear, the error was cleared.
However counting from “ 0005 is repeated on the display screen.
4 When pushing
TEST
button, the status becomes normal.
~ How to clear error of indoor unit
The error of indoor unit is cleared by
ON / OFF
button of the remote controller.
(Only error of the indoor unit connected with remote controller to be operated is cleared.)

Related product manuals