LED display on P.C. board (MCC-1570, 4-Way Casstte Type only)
1. D501 (Red)
D501 goes on at the same time when the power supply is turned on.
(Goes on with operation of the main microprocessor)
D501 flashes with 1-second interval (every 0.5 second) : When there is no EEPROM or write-in error
D501 flashes with 10-seconds interval (every 5 second) : In DISP mode
D501 flashes with 2-seconds interval (every 1 second) : During setting of function exchange
(EEPROM)
2. D403 (Red)
D403 goes on when power is supplied to the remote controller. (ON in hardware)
3. D503 (Yellow): Indoor/Outdoor central control
D503 goes on for 5 seconds at the first half during communication with the central controller.
D503 flashes for 5 seconds with 0.2-second interval at the latter half during communication with
outdoor unit. (Goes on for 0.1 second, goes off for 0.1 second)
4. D504 (Green): Remote controller communication
D504 goes on for 5 seconds at the first half during communication with remote controller.
(Header unit of group)
In the group indoor unit, D504 flashes for 5 seconds with 0.2-second interval at the latter half during
communication between header and follower unit. (Goes on for 0.1 second, goes off for 0.1 second)
High wall type wireless remote controller A-B selection>
Using 2 wireless remote controllers for the respective air conditioners, when the 2 air conditioners are closely
installed.
Wireless remote controller B setup
1. Push button on the indoor unit to turn the air conditioner ON.
2. Point the wireless remote controller at the indoor unit.
3. Push and hold CHK z button on the wireless remote controller by the tip of the pencil.
“00” will be shown on the display.
4. Push
z
during pushing CHK z .
“B” will be shown on the display and “00” will be disappear and the air conditioner will turn OFF.
The wireless remote controller B is memorized.
NOTE
Repeat above step to reset wireless remote controller to be A.
The wireless remote controllers do not display “A”.
The factory default of the wireless remote controllers is “A”.