EasyManua.ls Logo

Toshiba Carrier MMK-AP0093H2UL - Page 95

Toshiba Carrier MMK-AP0093H2UL
173 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
95
Check code
Location
of
detection
Description System status
Error detection
condition(s)
Check items (locations)
Main
remote
controller
Outdoor 7-segment display
Check code
Sub-code
L29 L29
Symbol O
signifies site of
IPDU error.
I/F Error in No. of
IPDUs
All stop Insufficient number of IPDUs
are detected when power is
turned on.
Check model setting of
P.C. board for servicing
outdoor I/F P.C. board.
Check connection of UART
communication connector.
Check A3-IPDU, fan IPDU,
and I/F P.C. board for
defect.
L30 L30
L31
Detected indoor
address
Indoor
unit
External
interlock of
indoor unit
Stop of
corresponding
unit
Signal is present at
external error input
terminal (CN80) for 1
minute.
When external device is
connected to CN80
connector:
1) Check for defect in
external device.
2) Check for defect in indoor
P.C. board.
When external device is not
connected to CN80
connector:
1) Check for defect in indoor
P.C. board.
––
I/F Extended IC
error
Continued
operation
There is part failure in P.C.
board (I/F).
Check outdoor P.C. board
(I/F).
P01
Indoor
unit
Indoor fan
motor error
Stop of
corresponding
unit
Check the lock of fan motor
(AC fan).
•Check wiring.
P03 P03
I/F Discharge
temperature
TD1 error
All stop Discharge temperature (TD1)
exceeds 239°F(115°C)
Check outdoor service
valves (gas side, liquid
side) to confirm full
opening.
Check outdoor PMVs
(PMV1, 2, 4) for clogging.
Check resistance
characteristics of TD1
sensor.
Check for insufficiency in
refrigerant quantity.
Check for defect in 4-way
valve.
Check for leakage of SV4
circuit.
Check SV4 circuit (wiring
or installation error in
SV41, SV42 or SV43)
.
A3-IPDU
Fan
IPDU
O
O
O
O
O
O
O
O
231
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
01
02
03
04
05
06
07
08
09
0A
0B
0C
0D
0E
0F

Related product manuals