–16–
EN
H16 H16
01: TK1 oil circuit system error
02: TK2 oil circuit system error
03: TK3 oil circuit system error
04: TK4 oil circuit system error
Oil level detective circuit error I/F
H25 H25 — TD3 miswiring I/F
L03 — — SIM Indoor center unit duplicated Indoor
L04 L04 — SIM Outdoor line address duplicated I/F
L05 — — SIM
Duplicated indoor units with priority
(Displayed in indoor unit with priority)
I/F
L06 L06 No. of indoor units with priority SIM
Duplicated indoor units with priority
(Displayed in unit other than indoor unit with priority)
I/F
L07 — — SIM Group line in individual indoor unit Indoor
L08 L08 — SIM Indoor group/Address unset Indoor, I/F
L09 — — SIM Indoor capacity unset Indoor
L10 L10 — SIM Outdoor capacity unset I/F
L17 L17 — SIM Outdoor unit model unmatch error I/F
L20 — — SIM Duplicated central control addresses Indoor
L28 L28 — SIM Over No. of connected outdoor units I/F
L29 L29 SIM No. of IPDU error I/F
L30 L30 Detected indoor address SIM Indoor outside interlock Indoor
— L31 — — Extended I/C error I/F
P01 — — ALT Indoor fan motor error Indoor
P03 P03 — ALT Discharge temp. TD1 error I/F
P04 P04
01: Comp. 1 side
02: Comp. 2 side
03: Comp. 3 side
ALT High-pressure SW system operation IPDU
P05 P05
00: Detected phase loss
ALT
Phase loss error/interruption of power supply
I/F
01: Comp. 1 side
02: Comp. 2 side
03: Comp. 3 side
Inverter DC voltage (Vdc) error
P07 P07
01: Comp. 1 side
02: Comp. 2 side
03: Comp. 3 side
ALT Heat sink overheat error IPDU, I/F
P10 P10 Detected indoor address ALT Indoor overflow error Indoor
P12 — — ALT Indoor fan motor error Indoor
P13 P13 — ALT Outdoor liquid back detection error I/F
P15 P15
01: TS condition
02: TD condition
ALT Gas leak detection I/F
P17 P17 — ALT Discharge temp. TD2 error I/F
Check code Wireless remote control
Check code name Judging device
Wired remote
control display
Outdoor 7-segment display
Sensor block display of
receiving unit
Auxiliary code
Operation
Timer
Ready
Flash
A3-IPDU
Fan
IPDU
123
01
02
03
04
05
06
07
08
09
0A
0B
0C
0D
0E
0F
: IPDU error
Error detected by TCC-LINK central control device
TCC-LINK : TOSHIBA Carrier Communication Link.
P18 P18 — ALT Discharge temp. TD3 error I/F
P19 P19 Detected outdoor unit number ALT 4-way valve inverse error I/F
P20 P20 — ALT High-pressure protective operation I/F
P22 P22
0 :IGBT circuit
1 :Location detection circuit
error
3 :Motor lock-up error
4 :Motor current was
detected.
C :Abnormal temperature was
detected by the TH sensor.
D :TH sensor error
E : Inverter DC voltage error
(outdoor unit fan)
Caution)
Although letters 0 to F appear at
locations indicated by “ ”,
please ignore them.
ALT Outdoor fan IPDU error IPDU
P26 P26
01: Comp. 1 side
02: Comp. 2 side
03: Comp. 3 side
ALT G-TR short protection error IPDU
P29 P29
01: Comp. 1 side
02: Comp. 2 side
03: Comp. 3 side
ALT Comp position detective circuit system error IPDU
P31 P31 — ALT
Other indoor unit error
(Group follower unit error)
Indoor
Check code Wireless remote control
Check code name Judging device
Wired remote
control display
Outdoor 7-segment display
Sensor block display of
receiving unit
Auxiliary code
Operation
Timer
Ready
Flash
C05 — — — Sending error in TCC-LINK central control device TCC-LINK
C06 — — — Receiving error in TCC-LINK central control device TCC-LINK
C12 — — —
Batch alarm of general-purpose equipment control
interface
General-purpose
equipment I/F
P30
Differs according to error contents of unit with occurrence of alarm Group control branching unit error
TCC-LINK
— — (L20 is displayed) Duplicated central control addresses
Check code Wireless remote control
Check code name Judging device
Wired remote
control display
Outdoor 7-segment display
Sensor block display of
receiving unit
Auxiliary code
Operation
Timer
Ready
Flash
31-EN 32-EN
+00EH99876101-2_00Ta.book Page 16 Monday, September 1, 2014 10:15 AM