How to change an indoor unit address by using a wired remote control
Use this method to change the address of indoor units (one to one or group control) that have had the original
address set automatically.
This procedure must be done while the units are not operating.
1 Simultaneously push and hold the “SET
S
E
T
”, “CL
CL
”, and “TEST
TEST
buttons for more than 4
seconds. If there are 2 or more units in a group, the first “UNIT No. indicated is the header
unit.
Ø
2 Push the left end of the “UNIT LOUVER
UNIT LOUVER
button repeatedly to select an indoor unit
address to change. If 2 or more units are controlled in a group the fan and louvers of the
selected unit will be energized.
Ø
3
Push the TEMP. / buttons repeatedly to select 13 for CODE No..
Ø
4
Push the TIME / buttons repeatedly to change the value indicated in the SET DATA sec-
tion.
5 Push the “SET
S
E
T
button, to save address.
Ø
6
Push left and of the “UNIT LOUVER
UNIT LOUVER
button repeatedly to select another indoor unit
addresses to change. Repeat steps 4 through 6 to continue changing indoor unit address and
make each of them unique.
7 Push the left end of the “UNIT LOUVER
UNIT LOUVER
button to review/confirm the revised ad-
dresses.
Ø
8
If the addresses have been changed correctly, push the “TEST
TEST
button to finish the proce-
dure.
Ø