Muffler
RAV-SP300AT2-UL
∗ This compressor has 4-pole motor. The value when compressor frequency (Hz) is measured by a clamp
meter becomes 2 times of No. of compressor revolutions (rps).
RAV-SP360AT2-UL, RAV-SP420AT2-UL
∗ This compressor has 4-pole motor. The value when compressor frequency (Hz) is measured by a clamp
meter becomes 2 times of No. of compressor revolutions (rps).
RAV-SP300AT2-UL, RAV-SP360AT2-UL, RAV-SP420AT2-UL
Standard
Cooling Overload
Low load
Standard
Heating Overload
Low load
Pressure
(psi) (MPa)
Pd Ps Pd Ps
372.7 143.6 2.57 0.99
478.5 158.1 3.30 1.09
252.3 108.8 1.74 0.75
336.4 105.9 2.32 0.73
466.9 169.7 3.22 1.17
314.7 43.5 2.17 0.30
Pipe surface temperature °F (°C)
Discharge Suction
Indoor heat Outdoor heat
exchanger exchanger
(TD) (TS) (TC) (TL) (TE)
150.8 57.2 53.6 111.2 104.0
(66) (14) (12) (44) (38)
172.4 48.2 55.4 120.2 109.4
(78) ( 9) (13) (49) (43)
114.8 44.6 41.0 89.6 77.0
(46) ( 7) ( 5) (32) (25)
149.0 37.4 102.2 35.6 37.4
(65) ( 3) (39) ( 2) ( 3)
163.4 66.2 129.2 57.2 59.0
(73) (19) (54) (14) (15)
188.6 5 100.4 6.8 8.6
(87) (–15) (38) (–14) (–13)
Compressor
drive revolution
frequency
(rps)
38
53
21
43
26
71
Indoor
fan
HIGH
HIGH
LOW
HIGH
LOW
HIGH
Indoor/Outdoor
temp. conditions
(DB/WB) °F (°C)
Indoor Outdoor
80.6/66.2 95/–
(27/19) (35/–)
89.6/75.2 109.4/–
(32/24) (43/–)
64.4/59.9 23/–
(18/15.5) (–5/–)
68/– 44.6/42.8
(20/–) (7/6)
86/– 75.2/64.4
(30/–) (24/18)
59/– 5/–
(15/–) (–15/–)
Standard
Cooling Overload
Low load
Standard
Heating Overload
Low load
Pressure
(psi) (MPa)
Pd Ps Pd Ps
394.4 130.5 2.72 0.90
484.3 155.2 3.34 1.07
253.8 110.2 1.75 0.76
375.6 100.1 2.59 0.69
453.9 152.3 3.13 1.05
348.0 30.45 2.40 0.21
Pipe surface temperature °F (°C)
Discharge Suction
Indoor heat Outdoor heat
exchanger exchanger
(TD) (TS) (TC) (TL) (TE)
163.4 53.6 50 114.8 100.4
(73) (12) (10) (46) (38)
176.0 48.2 55.4 123.8 113.0
(80) ( 9) (13) (51) (45)
116.6 46.4 42.8 91.4 77.0
(47) ( 8) ( 6) (33) (25)
167 37.4 109.4 35.6 35.6
(45) ( 3) (43) ( 2) ( 2)
161.6 60.8 127.4 53.6 55.4
(72) (16) (53) (12) (13)
206.6 –7.6 107.6 –2.2 –0.4
(97) (–22) (42) (–19) (–18)
Compressor
drive revolution
frequency
(rps)
51
55
21
53
26
90
Indoor
fan
HIGH
HIGH
LOW
HIGH
LOW
HIGH
Indoor/Outdoor
temp. conditions
(DB/WB) °F (°C)
Indoor Outdoor
80.6/66.2 95/–
(27/19) (35/–)
89.6/75.2 109.4/–
(32/24) (43/–)
64.4/59.9 23/–
(18/15.5) (–5/–)
68/– 44.6/42.8
(20/–) (7/6)
86/– 75.2/64.4
(30/–) (24/18)
59/– 5/–
(15/–) (–15/–)