– 96 –
No.
i
Part name
Compressor
Compressor lead
(Continued)
Procedure
2. Mounting of compressor
1) Mount the compressor in the reverse
procedure of removal.
NOTES:
∗ After exchange of the compressor, be sure to
exchange the compressor lead. (Repair part
code of compressor lead: 43160591)
In this time, wrap the ferrite core with the
compressor lead wire by 4 times.
Using bundling band on the market, bind the
compressor lead. As the compressor lead is
long, be sure that the compressor lead does
not contact with the discharge pipe.
∗ Fix the removed each sensor and PMV coil
lead wire to the discharge pipe and the
suction pipe with the bundling band via the
pipe cover.
In this time, take note that each sensor and
PMV coil lead wire do not come to contact
with the discharge pipe and the reactor.
(For fixing to the discharge pipe, use the black
heat-proof pipe cover and the bundling band
for heat-proof which is sold on the market.)
∗ As shown in the right figure, mount the
sound-insulation plate (inner side, outer side)
by inserting between the compressor and the
piping, and between piping and the partition
plate.
∗ Put the compressor lead wire and the
compressor case thermo between inner side
and outer side of the sound-insulation as if
dropping them in.
Remarks
Compressor lead
Pass the soundproof plate (outer winding)
Pass the sound-insulation
plate (inner side) through
between compressor and
discharge pipe, suction pipe
and then put it on the other
side at this position.
Pipe cover, bundling band,
each sensor (TL, TO, TE, TS sensor)
PMV coil lead
Pipe cover, bundling band, TS sensor
Discharge pipe
Suction pipe
PMV coil lead
Set each sensor so that it does not