High-Wall Type
Installation Manual
–29–
Toshiba
Centrally control the system by the SDI series on their own
Setting for the terminating resistor is required.
Use switch SW01 for the setting.
Make the terminating resistor setting only for the indoor unit with the smallest line address number.
L1 L2 S
AB
U3 U4
U1
U3
U2
U4
AB
U3 U4
AB
U1
U3
U2
U4
L1 L2 S L1 L2 S
L1 L2 S
L1 L2 S L1 L2 S
Central
control
device
Central
control
device
Central control device: Up to 10 units
Refrigeration
system 1
Refrigeration
system 2
Refrigeration
system 3
Header
indoor
unit
Follower
indoor unit
Indoor unit
TCC-LINK adapter
(option)
Required for
indoor units other
than high wall type
Remote
controller wiring
Remote controller
Remote controller Remote controller
Group operation (up to 8 units)
(OFF at factory default)
Line address
SW01 bit1
Remarks
1
ON
Set bit1 of
SW01 to ON
2
OFF
Factory default
Outdoor unit
29-EN
+001111052201_00Ta.book Page 29 Friday, November 20, 2009 11:45 AM