NO. Item Specification outline Remarks
4
Based on the difference between TA and Ts, the operation
c
apacity is determined b
y the outdoor unit.
Automatic
capacity
control
Ts: Temperature set by
remote controller.
TA: Room temperature.
TA
(˚F)
+4
TA
(˚F)
+2
+2
Ts
Ts
2
2 4
COOL HEAT
S3
S5
S7
S9
SB
SD
SF
S0
SD
SB
S9
S7
S5
S3
S0
(TF type)
TF : Temperature of
discharge air
Ts : Temperature set by
remote controller
Based on the difference between TF and Ts, and the amount of temperature
change, the operation capacity is determined by the Fresh air intake to
command the operating frequency to the outdoor unit.
1) COOL operation
TF(n)-Ts(n) : Temperature difference n : Times of detection
TF(n-1)-TF(n) : Temperature change amount
2) HEAT operation
Ts(n)-TF(n) : Temperature difference amount n : Times of
detection
TF(n)-TF(n-1) : Temperature change amount
The Thermostat OFF will be activated only when Forced Thermostat OFF
conditions are satis
ed.
Forced Thermo-
OFF
(TF type)
The Forced thermostat OFF will be activated when conditions below are satised.
(1) Outdoor / Suction air temp. (TA)
COOL ・・・ When TA 66°F (T α c)
HEAT ・・・ When TA 59°F (T α h) or when TA 14°F
(2) Outdoor / Suction air temp. (TA) and temperature set by remote controller (Ts)
COOL ・・・ When TA Ts + 37°F (T β c)
HEAT ・・・ When TA Ts 37°F (T β h)
(3) Temperature of discharge air (TF)
COOL ・・・ When TF 37°F (T γ c)
HEAT ・・・ When TF 14F (T γ h)
CODE No. (DN)
Tαc : (DN)402=0019
Tαh : (DN)403=0015
Tβc : (DN)404=0003
Tβh : (DN)405=0003
Tγc : (DN)406=0003
Tγh : (DN)407=0060
5
(TA type)
- 27 -