For TA and TF type, the set temperature can be changed according to the 0 - 10 V input of AI3.
In the set temperature with the remote controller and this control, the post-setting is prioritized.
The set temperature can be changed only for cooling and heating operations.
To use this control, set DN [4A9] = 1.
Terminal AO1 / AO1: FAN speed 0 - 10 V output
CAUTION
The impedance of the device that receives the 0 - 10 V output signal shall be 10 kΩ or more.
Each FAN speed is output at 0 - 10 V.
The ripple voltage of 0 - 10 V is less than ± 30 mV of the set
voltage. Connect equipment that is not affected by this
ripple voltage.
The output voltage can be changed by DN setting [4A4] to
[4A6].
* Terminal AO2 / AO2 cannot be used.
FAN
speed
Output Initial
Applicable range
(Def) (Def)
HH 9 V 4A4 (0009) 8 V (0008) - 10 V (0010)
H 6 V 4A5 (0006) 4 V (0004) - 7 V (0007)
L 2 V 4A6 (0002) 1 V (0001) - 3 V (0003)
STOP 0 V - -
TA type
10.00
9.70
8.95
8.20
TF type
7.45
6.70
5.95
5.20
4.45
3.70
2.95
2.20
1.45
0.70
0.00
9.50
8.75
8.00
7.25
6.50
5.75
5.00
4.25
3.50
2.75
2.00
(V)
Set temp
Heating / Cooling
1.25
0.50
(V)
10.00
9.70
8.95
8.20
7.45
6.70
5.95
5.20
4.45
3.70
2.95
2.20
1.45
0.70
0.00
9.50
8.75
8.00
7.25
6.50
5.75
5.00
4.25
3.50
2.75
2.00
1.25
0.50
86°F (30°C) / 77°F (25°C)
84°F (29°C) / 75°F (24°C)
82°F (28°C) / 73°F (23°C)
81°F (27°C) / 72°F (22°C)
79°F (26°C) / 70°F (21°C)
77°F (25°C) / 68°F (20°C)
75°F (24°C) / 66°F (19°C)
73°F (23°C) / 64°F (18°C)
72°F (22°C) / 63°F (17°C)
70°F (21°C) / 61°F (16°C)
68°F (20°C) / 59°F (15°C)
66°F (19°C) / 57°F (14°C)
64°F (18°C) / 55°F (13°C)
Set temp
Heating / Cooling
70°F (21°C) / 70°F (21°C)
68°F (20°C) / 68°F (20°C)
66°F (19°C) / 66°F (19°C)
64°F (18°C) / 64°F (18°C)
64°F (18°C) / 64°F (18°C)
84°F (29°C) / 84°F (29°C)
82°F (28°C) / 82°F (28°C)
81°F (27°C) / 81°F (27°C)
79°F (26°C) / 79°F (26°C)
77°F (25°C) / 77°F (25°C)
75°F (24°C) / 75°F (24°C)
73°F (23°C) / 73°F (23°C)
72°F (22°C) / 72°F (22°C)
TCB-IFDMR01UP-UL
(Terminal block with relay)
Shield wire MAX. 656'2 (200 m)
Locally procured
Output
0 - 10 V
0 - 10 V Signal (+)
AO1
AO1
GND (-)
- 44 -