NO. Item Specification outline Remarks
4
Based on the difference between TA and Ts, the operation
c
apacity is determined b
y the outdoor unit.
Automatic
capacity
control
Ts: Temperature set by
remote controller.
TA: Room temperature.
TA
(˚F)
+4
TA
(˚F)
+2
+2
Ts
Ts
–2
–2 –4
COOL HEAT
S3
S5
S7
S9
SB
SD
SF
S0
SD
SB
S9
S7
S5
S3
S0
(TF type)
TF : Temperature of
discharge air
Ts : Temperature set by
remote controller
Based on the difference between TF and Ts, and the amount of temperature
change, the operation capacity is determined by the Fresh air intake to
command the operating frequency to the outdoor unit.
1) COOL operation
TF(n)-Ts(n) : Temperature difference n : Times of detection
TF(n-1)-TF(n) : Temperature change amount
2) HEAT operation
Ts(n)-TF(n) : Temperature difference amount n : Times of
detection
TF(n)-TF(n-1) : Temperature change amount
The Thermostat OFF will be activated only when Forced Thermostat OFF
conditions are satisfi
ed.
Forced Thermo-
OFF
(TF type)
The Forced thermostat OFF will be activated when conditions below are satisfied.
(1) Outdoor / Suction air temp. (TA)
・ COOL ・・・ When TA ≦ 66°F (T α c)
・ HEAT ・・・ When TA ≧ 59°F (T α h) or when TA ≦ 14°F
(2) Outdoor / Suction air temp. (TA) and temperature set by remote controller (Ts)
・ COOL ・・・ When TA ≦ Ts + 37°F (T β c)
・ HEAT ・・・ When TA ≧ Ts − 37°F (T β h)
(3) Temperature of discharge air (TF)
・ COOL ・・・ When TF ≦ 37°F (T γ c)
・ HEAT ・・・ When TF ≧ 140°F (T γ h)
CODE No. (DN)
Tαc : (DN)「402」=0019
Tαh : (DN)「403」=0015
Tβc : (DN)「404」=0003
Tβh : (DN)「405」=0003
Tγc : (DN)「406」=0003
Tγh : (DN)「407」=0060
5
(TA type)