Terminal DI1 / DI1: Safety contact (Normal close)
MODE 1 (Normally close, DC12 V) *When Bit1 of SW505 is OFF
If this contact is open for more than 1 minute, the check code P10 is generated and the Dx-coil controller switches off
automatically.
MODE
2 (Normally open, DC12 V) *When Bit1 of SW505 is ON
If this contact is short for more than 1 minute, the check code P10 is generated and the Dx-coil controller switches of
f
automatically.
SW701 SW505 Function
OFF
OFF
The coil drive voltage is input to the relay arranged locally for DI1, and judge that the close is
positive. (Default)
Relay: Local arrangement
ON
The coil drive voltage is not input to the relay arranged locally for DI1, and judge that the open is
positive.
Relay: Local arrangement
ON
OFF
For DI1, short-circuit the (+) signal voltage and DI1 (-) GND with a SW or harness, and judge
that the close is positive.
Relay: Not required
* The signal voltage is DC12 V ± 10%, and it is necessary to add a SW element to the signal line.
ON
For DI1, open the (+) signal voltage and DI1 (-) GND, and judge that the open is positive.
Relay: Not required
* The signal voltage is DC12 V ± 10%, and it is necessary to add a SW element to the signal line.
SW505
SW701
SW505
Bit1:
OFF
SW701
SW505
Bit1:
OFF
MAX. 328'1" (100 m)
Locally procured
Normally closed
GND
SIGNAL (12 V)
DI1
DI1
MAX. 328'1" (100 m)
Locally procured
SIGNAL (+)
SIGNAL (-)
Signal Voltage (DC12 V ± 10%)
DI1
DI1
GND
Normally closed
SW701
SW505
Bit1:
ON
SW701
SW505
Bit1:
ON
MAX. 328'1" (100 m)
Locally procured
Normally open
GND
SIGNAL (12 V)
DI1
DI1
MAX. 328'1" (100 m) Locally procured
SIGNAL (+)
SIGNAL (-)
Signal Voltage (DC12 V ± 10%)
DI1
DI1
GND
Normally open
- 40 -