Terminal DI2 / DI2: External trouble Input
An AHU fan operation monitor (Field supply), could be attached at this dry contact terminal (For example, the
abnormality of the fan motor). A closed contact generates the check code L30.
Terminal DI3 / DI3: Forced thermostat OFF Input
When signal input, AHU is in “thermostat-off” status forcibly.
Terminal DI4 / DI4: Notice code Input
If there is input, a spanner mark will be displayed on the remote controller. The system will not stop.
Check “DN settings” for the setting method.
Terminal DI5 / DI5: Operation Mode Input (Cool / Heat)
Cool / Heat mode selection over a dry contact.
If the contact is short-circuited, system changes to heat mode.If the contact is open, system changes to cool mode.
Only cool mode and heat mode are available.
When Bit4 of SW502 is turned on in DDC type, capacity demand can be achieved by short-circuiting Terminals DI2 to
DI4.
* If all are short-circuited, the DI3 function has priority.
When SW701 is ON (no voltage), apply a voltage of DC12 V ± 10% and wiring as follows.
Function Terminal OPEN SHORT
Mode Input Cool / Heat DI5 / DI5 COOL mode active HEAT mode active
Short - circuit Cooling step Heating step
DI2 - DI2 2 4
DI3 - DI3 5 9
DI4 - DI4 11 13
MAX. 328'1" (100 m)
Locally procured
SIGNAL (+)
SIGNAL (-)
Signal Voltage (DC12 V ± 10%)
DI2 - DI4
DI2 - DI4
GND
Normally open
Terminal DI6 / DI6: External ON/OFF Input
When using with DDC, it starts by turning on this terminal
TCB-IFDMR01UP-UL
(Terminal block with relay)
MAX. 328'1" (100 m)
Locally procured
(Input, DC5 V)
DI6
DI6
Relay coil signal
- 41 -