Function CODE No. (DN Code) table (includes all functions needed to perform applied control on site)
TA TF DDC
01 Fi
lter display delay timer Yes Yes Yes
0001: 150H
0003: 5000H
0000: None
0002: 2500H
0004: 10000H
0000: None
02 Dirt
y state of filter Yes Yes Yes
0000: Standard
0001: High degree of dirt (Half of standard time)
0000: Standard
03 Cen
tral control address Yes Yes Yes
0001: No.1 unit to 0064: No.64 unit … TCC-LINK
0001: No.1 unit to 0128: No.128 unit … TU2C-LINK
00Un: Unfixed (When using U series remote controller)
0099: Unfixed (Other than U series remote controller)
00Un/0099: Unfixed *1
04
Sp
ecific indoor unit
priority
Yes No No 0000: No priority 0001: Priority 0000: No priority
0D
Ex
istence of [AUTO]
mode
Yes Yes No
0000: Provided 0001: Not provided
0001: Not provided
(Automatic selection from connected outdoor unit
0001: Not provided
10 T
ype Yes Yes Yes It will switch automatically depending on the SW501bit1,2 setting.
TAtype:0057
TFtype:0058
DDCtype:0059
11 In
door unit capacity Yes Yes Yes
0000: Unfixed 0001 to 0044
Refer to Indoor Unit Capacity DN code "11" list
0000: Unfixed
12 L
ine address Yes Yes Yes
0001: No.1 unit to 0030: No.30 unit … TCC-LINK 0001:
No.1 unit to 0128: No.128 unit … TU2C-LINK 00Un:
Unfixed (When using U series remote controller) 0099:
Unfixed (Other than U series remote controller)
00Un/0099: Unfixed *1
13 In
door unit address Yes Yes Yes
0001: No.1 unit to 0064: No.64 unit … TCC-LINK
0001: No.1 unit to 0128: No.128 unit … TU2C-LINK
00Un: Unfixed (When using U series remote controller)
0099: Unfixed (Other than U series remote controller)
00Un/0099: Unfixed *1
14 G
roup address Yes Yes Yes
0000: Individual 0001: Header unit of group
0002: Follower unit of group
00Un: Unfixed (When using U series remote controller)
0099: Unfixed (Other than U series remote controller)
00Un/0099: Unfixed *1
28
Au
tomatic restart of
power failure
Yes Yes Yes 0000: None 0001: Restart
0001: Restart
31 Ventilating fan control Yes Yes Yes 0000: Unavailable 0001: Available 0000: Unavailable
33 T
emperature unit select Yes Yes Yes
0000: °C
0001: °F
0001: °F
60
T
imer setting
(wired remote controller)
Yes Yes Yes
0000: Available 0001: Unavailable
(can be performed) (cannot be performed)
0000: Available
72 Fa
n Control during defrost No Yes No 0000: Fan ON 0001: Fan OFF
TA:0000
TF:0001
DDC:0000
92
F
an trouble Input
release condition
Yes Yes Yes 0000: Operation stopped 0001: Release signal received 0000: Operation stopped
D0
W
hether the power saving mode can be set
by the remote controller
Yes No No 0000: Invalid 0001: Valid
TA:0001
TF:0000
DDC:0000
FC
Com
munication protocol *2 Yes Yes Yes 0000:TCC-LINK 0003:TU2C-LINK 0000: TCC-LINK
180
Effective notice code
number 01
Yes Yes Yes 0000: None
181
Effective notice code
number 02
Yes Yes Yes 0000: None
182
Effective notice code
number 03
Yes Yes Yes 0000: None
183
Effective notice code
number 04
Yes Yes Yes 0000: None
184
Effective notice code
number 05
Yes Yes Yes 0000: None
185
Effective notice code
number 06
Yes Yes Yes 0000: None
186
Effective notice code
number 07
Yes Yes Yes 0000: None
187
Effective notice code
number 08
Yes Yes Yes 0000: None
188
Effective notice code
number 09
Yes Yes Yes 0000: None
189
Effective notice code
number 10
Yes Yes Yes 0000: None
1FB
Central device control state Yes Yes Yes
0000: No central device control (Remote controller use is possible)
0001: Central device control (Remote controller use is impossible)
0000: No central device
control
1FC Indoor Unit terminating resistance
Yes Yes Yes 0000: OFF 0001: ON 0000: OFF
At shipment
0000:None
0129:DI4/*DI4 Notice input ON (code 201)
0134:Tx sensor error (code 206)
DN Item
Setting allowed
Description
- 51 -