TA TF DDC
At shipmentDN Item
Setting allowed
Description
402
Cooling forced thermostat OFF temp. Tαc
(Minimum Outdoor/Suction air temp.) No Yes No
0018: 64°F(18°C) ~ 0025: 77°F(25°C) 0019: 66°F(19°C)
403
Heating forced thermostat OFF temp. Tαh
(Maximum Outdoor/Suction air temp.)
No Yes No
0000: 32°F(0°C) ~ 0017: 63°F(17°C ) 0015: 59°F(15°C)
404
Cooling design thermostat ON/OFF temp.
Tβc (Difference the setup temp. and
Outdoor/Suction air temp.)
No Yes No
0000: 32°F(0°C) ~ 0010: 50°F(10°C) 0003: 37°F(3°C)
405
Heating design thermostat ON/OFF temp.
Tβh
(Difference the setup temp.
and Outdoor/Suction air temp.)
No Yes No
0000: 32°F(0°C) ~ 0010: 50°F(10°C) 0003: 37°F(3°C)
406
Cooling forced thermostat OFF temp. Tγc
(Minimum Discharge air temp.)
No Yes No
-0015: 5°F(-15°C) ~ 0060: 140°F(60°C) 0003: 37°F(3°C)
407
Heating forced thermostat OFF temp. Tγh
(Maximum Discharge air temp.)
No Yes No
0000: 32°F(0°C) ~ 0060: 140°F(60°C) 0060: 140°F(60°C)
4A0 External input FAN control(4-20mA)
Yes Yes No
0000:None
0001:With FAN control by 4-20mA input (outdoor FAN control priority)
0002:With FAN control by 4-20mA input (priority is given to 4-20mA
input)
0000: None
4A1 Analog input FAN (H) control value
Yes Yes No 0013: 13mA
4A2
Analog input FAN (HH) control value
Yes Yes No
0004: +4mA
*1:Upper limit . DN[4A1] +
DN[4A2] 18mA
4A3
Analog input FAN (L) control value
Yes Yes No
0007: -7mA
*2:Lower limit. DN[4A1] -
DN [4A3]4mA
4A4 FAN speed Analog output value (HH)
Yes Yes No 0008: 8V ~ 0010:10V 0009:9V
4A5 FAN speed Analog output value (H)
Yes Yes No 0004: 4V ~ 0007:7V 0006:6V
4A6 FAN speed Analog output value (L)
Yes Yes No 0001: 1V ~ 0003:3V 0002:2V
4A7
TX (auxiliary temperature sensor) function
selection
Yes Yes
0000:None 0001:TA 0002:TF
0003:TCJ 0004:TC2
0000:None
4A8
TX (auxiliary temperature sensor) control
method selection
Yes
0000:Used in place of the temperature sensor selected in [4A7]
0001:Use the average value of the temperature sensor selected in
[4A7] for control
0000
4A9 Set temperature change function by 0-10V
Yes Yes No 0000:OFF  0001:ON 0000:OFF
4AA Heating set temperature shift by 0-10V input
Yes Yes No
-0010: 14°F(-10) ~ 0010: 50°F(10)
0000: 32°F(0)
4AB Cooling set temperature shift by 0-10V input
Yes Yes No
-0010: 14°F(-10) ~ 0010: 50°F(10) 0000: 32°F(0)
4AC
Operation prohibited from centralized
equipment
Yes Yes Yes 0000:approval 0001:NOT approval 0000:approval
4AD TC1 miss-attachment detection control
Yes Yes Yes 0000:No control  0001:With control 0000:No control
4AE Dx-Valve kit type name
Yes Yes Yes
0001:6~10Ton 0002:12~16Ton Depends on Ton settings
4AF Defrost signal output delay time
Yes Yes Yes 0000:No delay 0001:1 minute delay~ 0030:30 minute delay 0000:No delay
14
7
17
13
6
mA
18
H
L
HH
[DN]
Default
Details
[4A2] 0004 (4 mA) [4A1] +4 mA Applicable range +1 to +11
[4A1] 0013 (13 mA) Applicable range 7 mA to 16 mA
[4A3] 0007 (7 mA) [4A1] -7 mA Applicable range -1 to -12
*1: Upper limit. DN [4A1] + DN [4A2] 18 mA
*2: Lower limit. DN [4A1] - DN [4A3] 4mA
0003: 0.6~5Ton