64
G8000 Series Installation and Operation Manual
Step 4-5 continues the procedure to start the UPS.
STEP 4
Turn on the DC Input Breaker (72B) on the
external battery cabinet.
BATTERIES LED is “ON”.
STEP 5
*Press the “UPS” button for at least 0.5
seconds. This completes UPS startup
procedure
BYPASS LED is “OFF”.
UPS LED is “ON”.
NOTE
*If the AC switch does not function, contact
Toshiba or authorized representatives.
If the bypass power source is out of
specication, this operation will be inhibited.
In order to switch manually, press the “UPS”
button for 5 seconds or more.
CONVERTER
INVERTER
UPS
AC OUTPUT
BATTERIES
BYPASS INPUT
DISCHARGE
EQUAL CHARGE
FLOAT CHARGE
BYPASS
AC INPUT
AC
SWITCH
BYPASS
MOVE 72B TO ‘ON’ POSITION
CONVERTER
INVERTER
UPS
AC OUTPUT
BATTERIES
BYPASS INPUT
DISCHARGE
EQUAL CHARGE
FLOAT CHARGE
BYPASS
AC INPUT
AC
SWITCH
UPS SUPPLY
AC - Vo 480 V
AC - Io 50%
LED Key
- LED Off
- LED On
- LED Flash