106 ACE-tronics G9 ASD Installation and Operation Manual
V/f 5-Point Setting Voltage 2
Program Special V/f 5-Point Setting
The V/f 5-Point Setting Voltage 2 establishes the output voltage level that is to
be associated with the frequency setting of
F192 (V/f 5-Point Setting Frequency
2).
The F701 parameter setting will determine if the selection for this parameter
appears in the form of a Voltage (V) or as a Percentage (%) of the ASD rating.
The default setting is %.
See F190 and F191 for additional information on this setting.
Direct Access Number F193
Parameter Type — Numerical
Factory Default 0.0
Changeable During RunNo
Minimum — 0.0
Maximum — 100.0
Units — V or % (F701)
V/f 5-Point Setting Frequency 3
Program Special V/f 5-Point Setting
The Custom V/f 5-Point Setting Frequency 3 sets the frequency to be
associated with the voltage setting of parameter
F195 (V/f 5-Point Setting
Voltage 3).
See F190 and F191 for additional information on this setting.
Direct Access Number F194
Parameter Type — Numerical
Factory Default 0.00
Changeable During RunNo
Minimum — 0.00
Maximum — Max. Freq. (F011)
Units — Hz
V/f 5-Point Setting Voltage 3
Program Special V/f 5-Point Setting
The V/f 5-Point Setting Voltage 3 establishes the output voltage level that is to
be associated with the frequency setting of
F194 (V/f 5-Point Setting Frequency
3).
The F701 parameter setting will determine if the selection for this parameter
appears in the form of a Voltage (V) or as a Percentage (%) of the ASD rating.
The default setting is %.
See F190 and F191 for additional information on this setting.
Direct Access Number F195
Parameter Type — Numerical
Factory Default 0.0
Changeable During RunNo
Minimum — 0.0
Maximum — 100.0
Units — V or % (F701)
V/f 5-Point Setting Frequency 4
Program Special V/f 5-Point Setting
The Custom V/f 5-Point Setting Frequency 4 sets the frequency to be
associated with the voltage setting of parameter
F197 (V/f 5-Point Setting
Voltage 4).
See F190 and F191 for additional information on this setting.
Direct Access Number F196
Parameter Type — Numerical
Factory Default 0.00
Changeable During RunNo
Minimum — 0.00
Maximum — Max. Freq. (F011)
Units — Hz
V/f 5-Point Setting Voltage 4
Program Special V/f 5-Point Setting
The V/f 5-Point Setting Voltage 4 establishes the output voltage level that is to
be associated with the frequency setting of
F196 (V/f 5-Point Setting Frequency
4).
The F701 parameter setting will determine if the selection for this parameter
appears in the form of a Voltage (V) or as a Percentage (%) of the ASD rating.
The default setting is %.
See F190 and F191 for additional information on this setting.
Direct Access Number F197
Parameter Type — Numerical
Factory Default 0.0
Changeable During RunNo
Minimum — 0.0
Maximum — 100.0
Units — V or % (F701)