ACE-tronics G9 ASD Installation and Operation Manual 111
V/I Input Point 2 Rate
Program To r que Setpoints
This parameter is used to set the gain and bias of the V/I input terminal when
the V/I terminal is used as the control input while operating in the Torque
Control mode.
Torque Control is accomplished by establishing an associated V/f output
pattern for a given V/I input level.
This parameter sets V/I Input Point 2 Rate and is the output torque value that
is associated with the setting of V/I Input Point 2 Setting (
F203) when
operating in the Torque Control mode.
This value is entered as 0% to 250% of the rated torque.
See V/I Input Point 1 Rate (F205) for additional information on this setting.
Direct Access Number F206
Parameter Type — Numerical
Factory Default 100.00
Changeable During RunYes
Minimum — 0.00
Maximum — 250.00
Units — %
Frequency Mode 2
Program Fundamental Standard Mode Selection
This parameter is used to set the source of the frequency command signal to be
used as Frequency Mode 2 in the event that Frequency Mode 1 is disabled or
if Frequency Mode 2 is set up as the primary control parameter.
See F004 and F200 for additional information on this setting.
Settings:
V/I
RR
RX
EOI Keypad
RS485
Communication Option Board
RX2 Option (AI1)
Option V/I
UP/DOWN Frequency (ACE G9-120V-PCB)
Pulse Input (Option)
Pulse Input (Motor CPU)
Binary/BCD Input (Option)
Direct Access Number F207
Parameter Type — Selection List
Factory Default V/I
Changeable During RunYes
Frequency Mode Priority Switching Frequency
Program Fundamental Standard Mode Selection
This parameter establishes a threshold frequency that will be used as a reference
when determining when to switch the output frequency control source from the
Frequency Mode 1 setting to the Frequency Mode 2 setting.
See F200 for additional information on this setting.
Direct Access Number F208
Parameter Type — Numerical
Factory Default 0.10
Changeable During RunYes
Minimum — 0.10
Maximum — Max. Freq. (F011)
Units — Hz
F206 F208