130 ACE-tronics G9 ASD Installation and Operation Manual
Jog Stop Pattern
Program Frequency Jog
This parameter sets the stopping method used while operating in the Jog mode.
Note: This parameter setting is used for the Jog operation only. The
Emergency Off stopping method setting of parameter
F603 has
priority over this setting and changes made here do not affect the
function or setting of parameter
F603.
Settings:
Deceleration Stop
Coast Stop
DC Injection Braking Stop
Direct Access Number F261
Parameter Type — Selection List
Factory Default Deceleration Stop
Changeable During RunYes
Panel Operation Jog Mode
Program Frequency Jog
This parameter enables the Jog command to be received from the EOI. When
disabled the Jog command received from the EOI is ignored.
Jog commands may also be received from the ACE G9-120V-PCB. Priority as
to which is allowed to override the other is selected at
F106.
The priority selection at F106 enables the selected source for Jog control and
disables the other. The F106 setting overrides this parameter setting.
Settings:
Disabled
Enabled
Direct Access Number F262
Parameter Type — Selection List
Factory Default Disabled
Changeable During RunYes
F261 F262