ACE-tronics G9 ASD Installation and Operation Manual 161
Dynamic Braking Torque Limit 1
Program Torque Torque Limit
This parameter determines the source of the Regenerative Torque Limit
control signal.
If Setting is selected, the value set at F443 is used for this parameter.
Settings:
V/I
RR
RX
F443 Setting
Direct Access Number — F442
Parameter Type — Selection List
Factory Default — F443 Setting
Changeable During Run — Yes
Dynamic Braking Torque Limit 1 Level
Program To r que Torque Limit
This parameter provides a value to be used as the Regeneration Torque Limit
1 if
F443 Setting is selected at parameter F442.
Set this parameter to 250% to disable this function.
Direct Access Number — F443
Parameter Type — Numerical
Factory Default — 250.0 (Disabled)
Changeable During Run — Yes
Minimum — 0.00
Maximum — 249.9
Units — %
Power Running Torque Limit 2 Level
Program To r que Manual Torque Limit
This parameter is used to set the positive torque upper limit for the #2 motor
profile when multiple motors are controlled by a single ASD or when a single
motor is to be controlled by multiple profiles.
Direct Access Number — F444
Parameter Type — Numerical
Factory Default — 250.0 (Disabled)
Changeable During Run — Yes
Minimum — 0.00
Maximum — 250.0 (Disabled)
Units — %
Dynamic Braking Torque Limit 2 Level
Program To r que Manual Torque Limit
This parameter is used to set the negative torque upper limit for the #2 motor
profile when multiple motors are controlled by a single ASD or when a single
motor is to be controlled by multiple profiles.
Direct Access Number — F445
Parameter Type — Numerical
Factory Default — 250.0 (Disabled)
Changeable During Run — Yes
Minimum — 0.00
Maximum — 250.0 (Disabled)
Units — %
Power Running Torque Limit 3 Level
Program To r que Manual Torque Limit
This parameter is used to set the positive torque upper limit for the #3 motor
profile when multiple motors are controlled by a single ASD or when a single
motor is to be controlled by multiple profiles.
Direct Access Number — F446
Parameter Type — Numerical
Factory Default — 250.0 (Disabled)
Changeable During Run — Yes
Minimum — 0.00
Maximum — 250.0 (Disabled)
Units — %
F442 F446
efesotomasyon.com -Toshiba inverter,drive,servo,plc