ACE-tronics G9 ASD Installation and Operation Manual 163
Dynamic Braking Stall Prevention Mode
Program Protection Stall
The function of this parameter is to disable the Over-Voltage Stall (F305) and
the Over-Current Stall (F017) function during regeneration only.
Application-specific conditions may occur that warrant disabling the Stall
function during regeneration.
Settings:
Disabled (Stall During Dynamic Braking)
Enabled (No Stall During Dynamic Braking)
Direct Access Number F453
Parameter Type — Selection List
Factory Default Enabled
Changeable During RunYes
Current Control Proportional Gain
Program Feedback PG
This parameter sets the sensitivity of the ASD when monitoring the output
current to control speed.
The larger the value entered here, the more sensitive the ASD is to changes in
the received feedback.
Direct Access Number F458
Parameter Type — Numerical
Factory Default — (ASD-Dependent)
Changeable During RunNo
Minimum — 0.0
Maximum — 100.0
Speed Loop Proportional Gain
Program Feedback PG
During closed-loop operation, this parameter sets the response sensitivity of the
ASD when monitoring the output speed for control.
The larger the value entered here, the larger the change in the output speed for a
given received feedback signal.
Direct Access Number F460
Parameter Type — Numerical
Factory Default — (ASD-Dependent)
Changeable During RunNo
Minimum — 1
Maximum — 9999
Speed Loop Stabilization Coefficient
Program Feedback PG
During closed-loop operation, this parameter sets the response sensitivity of the
ASD when monitoring the output speed for control.
The larger the value entered here, the quicker the response to changes in the
received feedback.
Direct Access Number F461
Parameter Type — Numerical
Factory Default 100
Changeable During RunYes
Minimum — 1
Maximum — 9999
Load Moment of Inertia 1
Program Feedback PG
This parameter is used for calculating accel/decel torque when compensating
for load inertia while operating in the Drooping Control mode.
Direct Access Number F462
Parameter Type — Numerical
Factory Default 35
Changeable During RunYes
Minimum — 0
Maximum — 100
Second Speed Loop Proportional Gain
Program Feedback PG
During closed-loop operation, this parameter sets the sensitivity of the ASD
when monitoring the output speed for control.
The larger the value entered here, the more sensitive the ASD is to changes in
the received feedback.
Direct Access Number F463
Parameter Type — Numerical
Factory Default — (ASD-Dependent)
Changeable During RunNo
Minimum — 1
Maximum — 9999
F453 F463