166 ACE-tronics G9 ASD Installation and Operation Manual
RX2 Option (AI1) Input Bias
Program Frequency Speed Reference Setpoints
This parameter is used to fine tune the bias of the RX2 (AI1) input terminal
when this terminal is used as the control input while operating in the Speed
Control mode or the Torque Control mode.
This setting may be used to ensure that the zero level of the input source (pot,
pressure transducer, flow meter, etc.) is also the zero level setting of the ASD
system.
This is accomplished by setting the input source to zero and adjusting this
setting to provide a zero output from the ASD.
Direct Access Number F476
Parameter Type — Numerical
Factory Default 128
Changeable During RunYes
Minimum — 0
Maximum — 255
RX2 Option (AI1) Input Gain
Program Frequency Speed Reference Setpoints
This parameter is used to fine tune the gain of the RX2 (AI1) input terminal
when this terminal is used as the control input while operating in the Speed
Control mode or the Torque Control mode.
This setting may be used to ensure that the 100% level of the input source (pot,
pressure transducer, flow meter, etc.) is also the 100% level setting of the ASD
system.
This is accomplished by setting the input source to 100% and adjusting this
setting to provide an output of 100% from the ASD.
Direct Access Number F477
Parameter Type — Numerical
Factory Default 128
Changeable During RunYes
Minimum — 0
Maximum — 255
V/I Input Bias (AI2 Option Board Input)
Program Frequency Speed Reference Setpoints
This parameter is used to fine tune the bias of the Optional AI2 input terminal
when this terminal is used as the control input while operating in the Speed
Control mode or the Torque Control mode.
This setting may be used to ensure that the zero level of the input source (pot,
pressure transducer, flow meter, etc.) is also the zero level setting of the ASD
system.
This is accomplished by setting the input source to zero and adjusting this
setting to provide a zero output from the ASD.
Direct Access Number F478
Parameter Type — Numerical
Factory Default 128
Changeable During RunYes
Minimum — 0
Maximum — 255
V/I Input Gain (AI2 Option Board Input)
Program Frequency Speed Reference Setpoints
This parameter is used to fine tune the gain of the Optional AI2 input terminal
when this terminal is used as the control input while operating in the Speed
Control mode or the Torque Control mode.
This setting may be used to ensure that the 100% level of the input source (pot,
pressure transducer, flow meter, etc.) is also the 100% level setting of the ASD
system.
This is accomplished by setting the input source to 100% and adjusting this
setting to provide an output of 100% from the ASD.
Direct Access Number F479
Parameter Type — Numerical
Factory Default 128
Changeable During RunYes
Minimum — 0
Maximum — 255
F476 F479