EasyManua.ls Logo

Toshiba G9 - Page 193

Toshiba G9
298 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ACE-tronics G9 ASD Installation and Operation Manual 183
Annual Average Ambient Temperature
Program Special Special Parameters
This parameter is used in conjunction with a discrete output terminal setting to
notify the operator of the remaining useful life of critical components of the
ASD system.
With a discrete output terminal set to Part Replacement Alarm (see Table 10
on pg. 242) and the calculation derived from the parameter setting, maintenance
scheduling may be enhanced.
Settings:
Under 10° C (50° F) — 60,000 Hours
Under 20° C (68° F) — 60,000 Hours
Under 30° C (86° F) — 60,000 Hours
Under 40° C (104° F)60,000 Hours
Under 50° C (122° F)40,000 Hours
Under 60° C (140° F)2,666 Hours
Direct Access Number F634
Parameter Type — Selection List
Factory Default Under 30°
Changeable During RunNo
Rush Current Suppression Replay Activation Time
Program Special Special Parameters Rush Relay Current
Activation Time
At system startup, this parameter sets a time-delay for the start of the Rush
Relay activation in an attempt to allow the DC bus voltage to reach the normal
operating level before outputting a signal to the motor.
Direct Access Number F635
Parameter Type — Numerical
Factory Default 0.0
Changeable During RunNo
Minimum — 0.0
Maximum — 2.5
Units — Seconds
PTC1 Thermal Selection
Program Special Special Parameters PTC1 Thermal Selection
This parameter Enables/Disables the optional external thermal detection circuit
of the Expansion IO Card Option 1. A thermistor is connected from TH1+ to
TH1- of TB3 on the Expansion IO Card Option 1.
Should the thermistor resistance reading fall below 50Ω because of an over-
temperature condition or exceed 3000
Ω because of an open circuit an External
Thermal Fault (OH2) will be incurred.
Note: While this parameter is Enabled, the system cannot be restarted
until the thermistor value recovers to the level of 1.8 k
Ω from an
over-temperature condition. An Auto-Restart will not be
initiated subsequent to an External Thermal Trip (OH2). A
manual restart will be required in the event of an OH2 trip.
Settings:
Disabled
Detect Disconnect
Direct Access Number F637
Parameter Type — Selection List
Factory Default Disabled
Changeable During RunNo
F634 F637
efesotomasyon.com -Toshiba inverter,drive,servo,plc

Table of Contents

Related product manuals