200 ACE-tronics G9 ASD Installation and Operation Manual
Point 1 Setting
Program Communications Communication Reference Adjust
When enabled at F810, this parameter is used to allow the user to set the gain
and bias of the speed control input to the ASD when the speed control signal is
received via the source selected at
F810 (Communications).
Gain and Bias Settings
When operating in the Speed Control mode and using one of the control
sources from parameter
F810, the settings that determine the gain and bias of
the input signal are:
• Point 1 Frequency (F812),
• the communications input signal value that represents Point 1 Frequency:
(Point 1 Setting)
F811,
• Point 2 Frequency (F814), and
• the communications input signal value that represents Point 2 Frequency:
(Point 2 Setting)
F813.
Once set, as the input signal value changes, the output frequency of the ASD
will vary in accordance with the above settings.
This parameter sets the Reference input value (Point 1 Setting) that represents
Point 1 Frequency. This value is entered as 0 to 100% of the Reference input
value range.
Changes made to this parameter require that the power be cycled (off then on)
for the changes to take effect.
Direct Access Number — F811
Parameter Type — Numerical
Factory Default — 0
Changeable During Run — Yes
Minimum — 0
Maximum — 100
Units — %
Point 1 Frequency
Program Communications Communication Reference Adjust
This parameter is used to set the gain and bias of the Reference speed control
input.
This parameter sets Point 1 Frequency.
Changes made to this parameter require that the power be cycled (off then on)
for the changes to take effect.
See F811 for additional information on this setting.
Direct Access Number — F812
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — Max. Freq. (F011)
Units — Hz
Point 2 Setting
Program Communications Communication Reference Adjust
This parameter is used to set the gain and bias of the Reference speed control
input.
This parameter sets the Reference input value (Point 2 Setting) that represents
Point 2 Frequency. This value is entered as 0 to 100% of the Reference input
value range.
Changes made to this parameter require that the power be cycled (off then on)
for the changes to take effect.
See F811 for additional information on this setting.
Direct Access Number — F813
Parameter Type — Numerical
Factory Default — 100
Changeable During Run — Yes
Minimum — 0
Maximum — 100
Units — %
F811 F813