EasyManua.ls Logo

Toshiba G9 - Page 218

Toshiba G9
298 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
208 ACE-tronics G9 ASD Installation and Operation Manual
Block Write Data 1
Program Communications Communication
This parameter plays a role in the setup of the communications network by
establishing the type of data to be written to the ASD of the communications
link.
The communications network includes other ASDs and Host/Control computers
that monitor the status of the ASD(s), transfers commands, and loads or
modifies the parameter settings of the ASD.
Changes made to this parameter require that the power be cycled (off then on)
for the changes to take effect.
Settings:
None
FA00 (Command 1)
FA20 (Command 2)
FA01 (Frequency)
FA50 (TB Output)
FA51 (Analog Output)
Direct Access Number F870
Parameter Type — Selection List
Factory Default None
Changeable During RunYes
Block Write Data 2
Program Communications Communication
This parameter plays a role in the setup of the communications network by
establishing the type of data to be written to the ASD of the communications
link.
The communications network includes other ASDs and Host/Control computers
that monitor the status of the ASD(s), transfers commands, and loads or
modifies the parameter settings of the ASD.
Changes made to this parameter require that the power be cycled (off then on)
for the changes to take effect.
Settings:
None
FA00 (Command 1)
FA20 (Command 2)
FA01 (Frequency)
FA50 (TB Output)
FA51 (Analog Output)
Direct Access Number F871
Parameter Type — Selection List
Factory Default None
Changeable During RunYes
F870 F871