ACE-tronics G9 ASD Installation and Operation Manual 215
My Function Percent Data 4
Program My Function My Function Data
This parameter is used to set the trigger threshold level of the analog signal of
the My Function Percent Data 4.
The analog signal is selected using the Input Setting number from Table 10 on
pg. 242.
Direct Access Number F921
Parameter Type — Numerical
Factory Default — 0.00
Changeable During RunYes
Minimum — 0.00
Maximum — 200.00
Units — %
My Function Percent Data 5
Program My Function My Function Data
This parameter is used to set the trigger threshold level of the analog signal of
the My Function Percent Data 5.
The analog signal is selected using the Input Setting number from Table 10 on
pg. 242.
Direct Access Number F922
Parameter Type — Numerical
Factory Default — 0.00
Changeable During RunYes
Minimum — 0.00
Maximum — 200.00
Units — %
My Function Frequency Data 1
Program My Function My Function Data
This parameter is used to set the trigger threshold level of the analog signal of
the My Function Frequency Data 1.
The analog signal is selected using the Input Setting number from Table 10 on
pg. 242.
Direct Access Number F923
Parameter Type — Numerical
Factory Default — 0.00
Changeable During RunYes
Minimum — 0.00
Maximum — 200.00
Units — %
My Function Frequency Data 2
Program My Function My Function Data
This parameter is used to set the trigger threshold level of the analog signal of
the My Function Frequency Data 2.
The analog signal is selected using the Input Setting number from Table 10 on
pg. 242.
Direct Access Number F924
Parameter Type — Numerical
Factory Default — 0.00
Changeable During RunYes
Minimum — 0.00
Maximum — 200.00
Units — %
My Function Frequency Data 3
Program My Function My Function Data
This parameter is used to set the trigger threshold level of the analog signal of
the My Function Frequency Data 3.
The analog signal is selected using the Input Setting number from Table 10 on
pg. 242.
Direct Access Number F925
Parameter Type — Numerical
Factory Default — 0.00
Changeable During RunYes
Minimum — 0.00
Maximum — 200.00
Units — %
My Function Frequency Data 4
Program My Function My Function Data
This parameter is used to set the trigger threshold level of the analog signal of
the My Function Frequency Data 4.
The analog signal is selected using the Input Setting number from Table 10 on
pg. 242.
Direct Access Number F926
Parameter Type — Numerical
Factory Default — 0.00
Changeable During RunYes
Minimum — 0.00
Maximum — 200.00
Units — %
F921 F926