G9000 Installation and Operation Manual 79
Status message Meaning Guidance Buzzer
UF109 DC UNBALANCED Major unbalance of the neutral point voltage.
Detection of converter zero-sequence
overcurrent.
UPS CONTROL
CIRCUIT ERROR
Battery current unbalance.
Sudden change of the DC voltage level.
Detection of DC ground fault UF159 exceeds
10 seconds. UPS transfers to bypass.
Power supply voltage to IGBT driver PCB is
below the specified level.
CALL SERVICE
ENGINEER
Continuous
sound
Major Lit on
UF151
24 hours after input power restoration,
batteries does not reach float voltage level.
Unable to equalize the voltage of various
batteries after 24 hours.
Minor Flicker
UF154 CB2 ABNORMAL During UVR, status signal from CB2 is ON.
Minor Flicker
UF156
CHG.STOPPED
(BATTERY
OVERTEMP.)
UF157 failure persisted for over 2 hours. CHECK BATTERY
Intermittent
sound
Minor
Battery
abnormal
Flicker
UF157
BATTERY
OVERTEMPERATU
RE
Detection of overtemperature at the
batteries.
CHECK BATTERY
Intermittent
sound
Minor
Battery
abnormal
Flicker
UF158
BATTERY LIQUID
LOW
Low level of battery electrolyte solution. CHECK BATTERY
Intermittent
sound
Minor
Battery
abnormal
Flicker
UF159
Detection of DC ground fault. Chopper
operation is stopped.
UPS CONTROL
CIRCUIT ERROR
Abnormal behavior of DC current sensor.
CHG.STOPPED(DC
VOLT. ABNORMAL)
UF151 failure is running for over 24 hours.
Failure detection based on battery
self-check.
Battery voltage is abnormal.
CALL SERVICE
ENGINEER
Intermittent
sound
Minor Flicker
UF170
VDB SENSOR
ABNORMAL
Detection of a large variation of the
difference between control-only and
protection-only battery voltage.
CALL SERVICE
ENGINEER
Intermittent
sound
Minor Flicker
UF171
UPS CONTROL
CIRCUIT ERROR
Poor shared current in parallel chopper
circuit; or improper charging current.
CALL SERVICE
ENGINEER
Intermittent
sound
Minor Flicker
UF172
CHG. STOPPED
(DEVICE STATUS)
Energy storage device error.
CALL SERVICE
ENGINEER
Intermittent
sound
Minor Flicker