G9000 Installation and Operation Manual 81
Status message Meaning Guidance Buzzer
External
UPS CONTROL
CIRCUIT ERROR
AD reference has an abnormal value.
UPS CONTROL
CIRCUIT ERROR
Detection of an external interruption during
the software execution.
UPS CONTROL
CIRCUIT ERROR
Timer does not reset in the specified period
(WDT settings)
UPS CONTROL
CIRCUIT ERROR
Detection of an abnormal clock speed in the
DSP or FPGA.
UPS CONTROL
CIRCUIT ERROR
Control power supply voltage is below the
specified level.
Inverter voltage is out of the specified range.
CALL SERVICE
ENGINEER
Continuous
sound
Major Lit on
UF310
MMS backup control power supplies exhibit
abnormal condition.
CALL SERVICE
ENGINEER
Continuous
sound
Major Lit on
UF320
UPS CONTROL
CIRCUIT ERROR
Cable disconnection in the parallel interface
board during load supply.
UPS CONTROL
CIRCUIT ERROR
Major communication error during parallel
operation.
UPS CONTROL
CIRCUIT ERROR
Gate driver abnormal for phase U (Note 4)
UPS CONTROL
CIRCUIT ERROR
Gate driver abnormal for phase V (Note 4)
UPS CONTROL
CIRCUIT ERROR
Gate driver abnormal for phase W (Note 4)
UPS CONTROL
CIRCUIT ERROR
Gate driver abnormal for chopper (Note 4)
SMS backup control power supplies exhibit
abnormal.
CALL SERVICE
ENGINEER
Intermittent
sound
Minor Flicker
UF363
UPS CONTROL
CIRCUIT ERROR
Synchronization error signal is being
received for a considerable time.
UPS CONTROL
CIRCUIT ERROR
Minor communication error during parallel
operation.
Minor Flicker
UF372
UPS CONTROL
CIRCUIT ERROR
Unable to synchronize the inverter output
and the bypass voltage when the bypass is
CALL SERVICE
ENGINEER
Intermittent
sound
Minor Flicker
UF374
UPS CONTROL
CIRCUIT ERROR
Cable disconnection in the parallel interface
board.
UPS CONTROL
CIRCUIT ERROR
Unable to achieve synchronization for
parallel operation.
UPS CONTROL
CIRCUIT ERROR
No control response from another UPS
although its detection is possible.
UPS CONTROL
CIRCUIT ERROR
Overload detection signal is being received
continuously for a considerable time.
UPS CONTROL
CIRCUIT ERROR
No answer for sending synchronizing signal.
UPS CONTROL
CIRCUIT ERROR
Abnormal clock speed of the parallel control
board processor.