6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 977 -
SBOw
Oper
Cancel
origin
stSeld
sboClass (choiceoperate-once)
ctlmodel (choiceSBOes or SBOns )
sboClass can be found by scrolling down.
Figure 4.9-65 LN editing screen for SBO (for example)
Defining DIR mode
Figure 4.9-66 exemplifies the TPOS logic node saved as GGIO2701. In the DIR mode, the
following three items should be selected using GR-TIEMS:
Oper
origin
ctlmodel (choice DOes or DOns )
Figure 4.9-66 LN editing screen for DIR mode (for example)
(ii) Mapping output data
The user should group the TPOS01 signals with regard to GOOSE and REPORT; the user
should map them for IEC61850 communication using GR-TIEMS. Figure 4.9-43 illustrates
how to map a signal; it indicates that the signals for the TPOS01 function are required to map
for IEC 61850 communication.