6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 1005 -
Table 4.11-11 Mapping signals for SPCSO1 object
Object_reference
Attribute
Type
FC
Signal Number
Signal Name
Ctrl/GAPC1$SPCSO1$origin
orCat
orCategory
ST
523001 300D011008
ASEQ01_ORCAT
Ctrl/GAPC1$SPCSO1$origin
orIdent
Octet64
ST
523001 6A0D011009
ASEQ01_ORIDENT
Ctrl/GAPC1$SPCSO1
stVal
BOOLEAN
ST
523001 000D011001
ASEQ01_ACC_EXEC
Ctrl/GAPC1$SPCSO1
q
Quality
ST
523001 310D011005
ASEQ01-QUALITY
Ctrl/GAPC1$SPCSO1
t
Timestamp
ST
523001 900D011006
ASEQ01_TIME
Ctrl/GAPC1$SPCSO1
stSeld
BOOLEAN
ST
523001 000D011D90
ASEQ01_STSELD
Note: Status (ST) is defined in the function constraint (FC) of the IEC 61850 standard.
Drag and drop
Figure 4.11-8 orCat attribute mapped into SPCSO1 object of GAPC1
(iii) Mapping input data
The ASEQ1 function can receive three commands select, operate, and cancel. Thus, the user
should map the input-point “ASEQ01_CONTROL_REQ. Table 4.11-12 shows the input-point
ASEQ01_CONTROL_REQ and the Object reference “Ctrl/GAPC1$SPCSO1”; the user should
map the input-point to the Object references with attributes CO and CF under FC. Figure 4.11-9
shows how to map a signal.
Note: The attribute is defined in the IEC 61850 standard; CO stands for Control
and CF stands for Configuration in the functional constraint (FC).