6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 1038 -
Setting [Pol-1CT] = Positive
Busbar
1CT
VCT
CT
I
a
I
b
I
c
Line1
CB#2
CB
CB#1
I
a2
I
b2
I
c2
2CT
I
e
1CT-Ie
I
e2
2CT-Ie
Busbar
Line2
I
em
CT-Iem
Setting [Pol-1CT-Ie] = Positive
Setting [Pol-2CT] = Positive
Setting [Pol-2CT-Ie] = Positive
Setting [Pol-CT-Iem] = Positive
Figure 5.2-16 Positive polarity settings in 1.5CB arrangement in VCT11B
Table 5.2-1 VCT settings provided with FEP_COMMON
FEP_COMMON (Function ID: 7F0001)
1CB
1CB or 1.5CB
Setting item
Range
Uni
ts
Contents
Settings in
VCT12B
Settings in
VCT11B
APPL-Ves2
Off / Ve / Vs2
Voltage input either Ve pr Vs
Vs2
Vs2
APPL-CTSELECT
1CT / 2CT
Selection of either 1CB or 1.5CB
(Not available)
2CT
Polarity
Pol-1CT
Negative / Positive
1CT Polarity
Positive
Positive
setting
Pol-1CT-Ie
Negative / Positive
Ie Polarity
Positive
Positive
Pol-2CT
Negative / Positive
2CT Polarity
(Not available)
Positive
Pol-2CT-Ie
Negative / Positive
Ie2 Polarity
(Not available)
Positive
Pol-CT-Iem
Negative / Positive
Iem Polarity
Positive
Positive
Note: For more information about the VCT11B and VCT12B, see the preceding section.