6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 1043 -
4. 1000Base-LX module (LC plug)
A pair of optic fiber cables is required. The 1000Base-LX module can be used for the GR-TIEMS
operation or the LAN communication. Use SM mode fiber when long distance is required.
C11
C12
Figure 5.3-7 1000Base-LX module
5. RS485 module
RS485 module has a PCB connector. The module should be connected with a shielded-twisted-
pair cable; it is used for the communication of the IEC60870-5-103. The terminal arrangement
and references are shown below. The cable sheath should be connected with the frame ground
(FG) in the IED case. For the use of the a shielded-twisted-pair cable, the user should note that
the total length should be less than 1200 meter (0.75 miles); the terminal resistor (150 ohms)
should be connected when any connector is not connected. For setting the parameters, see
Chapter
Communication protocol: RS485 communication
.
C11
C12
Figure 5.3-8 RS485 connection and module
Bottom
Top
a. View from connector edge
b. Port circuit
A1
A2
A3
B1
B2
B3
A1
A2
A3
B1
B2
B3
PCB connector
Sheath
Frame ground (FG)
COM-A(+)
COM-B()
COMM(GND)
0V
Sheath
A cable for
an IED
A cable for
another
IED