6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 1054 -
(i) Setting threshold level
For Standard type (the BI1A module and others)
The voltage level "High or Low", which tells a threshold of pick up / drop off, is selectable using
the selection switch [THRES_Lvl].
Table 5.4-5 shows the threshold voltage of picking-up/dropping-off for binary inputs at the high
and low level. This also shows how to set them with the selection switch.
Table 5.4-5 Threshold voltage of picking-up / dropping-off for binary inputs
(a) In the case of DC rated voltage “110-250 Vdc”
Voltage level
Threshold voltage of picking-up / dropping-off for binary inputs
How to set
Note
High
Typical 136V
Selection switch
[THRES_Lvl] = High
Low
Typical 71V
Selection switch
[THRES_Lvl] = Low
This is default.
(b) In the case of DC rated voltage “24-60 Vdc”
Voltage level
Threshold voltage of picking-up / dropping-off for binary inputs
How to set
Note
High
Typical 30V
Selection switch
[THRES_Lvl] = High
Low
Typical 15V
Selection switch
[THRES_Lvl] = Low
This is default.