EasyManua.ls Logo

Toshiba GR200 Series - (iii) Lighting LEDs on F1 to F7

Toshiba GR200 Series
1770 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 1095 -
BO1_SOURCE
200B01 310200E11D
Function key logic for F1
(Function ID: 240001)
PLC connection point in BO1
≥1
&
[BO1_CPL]
Off
On
&
DRIVER
BO1
Signal designated by
setting [Input signal 1]
[Input signal 2]
[Input signal 3]
[Input signal 4]
[Input signal 5]
[Input signal 6]
[Input signal 7]
[Input signal 8]
Signal to the
device
≥1
BO1
(200B01_8002001112)
BO1-RB
(200B01_8002001113)
BO1 circuit at IO_SLOT1 (Function ID: 200B01)
Terminal and
wire
To contact health
check
F1
Pressing the F1 key
F1 SIGNAL
(240001_ 3100001737)
Setting Data ID F1
SIGNAL for the
[Input signal 1]
Setting Data ID
BO1_SOURCE
for the [Signal]
[Logic]
Instant
&
Toggle
FUNC-KEY1
(240001_ 3100001730)
&
Figure 5.6-3 F1 key connected with the BO1
Note: The BO1 circuit is used just for an explanation; it is discussed in Chapter
Technical description: Binary IO module
.
Note: When the user wishes to inject the signal at the PLC connection point of the BO1-
SOURCE (200B01 31200E11D at the IO#1 slot), the user should set the BO1-
SOURCE (200B01 31200E11D) for the setting [Signal] of the F1 key. Then, set Off
for the scheme switch [BO1_CPL]
The user can select either Toggle or Instant modes for the signal generation using scheme
switch [LOGIC], as shown in Table 5.6-4. Thus, the user can substitute F1-SIGNAL (240001
310001737) for the FUNC-KEY1 SIGNAL (240001 310001730), provided the Toggle mode
is preferred. In the Table 5.6-7 the other FUNC-KEY2 to FUNC-KEY7 are shown.
Table 5.6-4 Signal mode selection using setting [LOGIC]
Setting
Generated signal corresponding to pressing the function key
Toggle
Pressing Key
Binary signal
Instant
Pressing Key
Binary signal
(iii) Lighting LEDs on F1 to F7
Figure 5.6-4 shows the F1 to F7 LED logics. Programing to light the LEDs (F1 to F7) is the
same as the programing of the LED indicators (#3 to #26) (for the programming, see section
5.6.2). As a default, e.g., the FUNC-KEY1 (240001 310001730) is set for the setting [Input
signal 1] of the F1 LED logic. The LED-F2 to F7 points are listed in Table 5.6-8.