- 1095 -
Function key logic for F1
(Function ID: 240001)
PLC connection point in BO1
Signal designated by
setting [Input signal 1]
“BO1”
(200B01_8002001112)
“BO1-RB”
(200B01_8002001113)
BO1 circuit at IO_SLOT1 (Function ID: 200B01)
“F1 SIGNAL”
(240001_ 3100001737)
Setting Data ID “F1
SIGNAL” for the
[Input signal 1]
Setting Data ID
“BO1_SOURCE”
for the [Signal]†
“FUNC-KEY1”
(240001_ 3100001730)
Figure 5.6-3 F1 key connected with the BO1‡
‡Note: The BO1 circuit is used just for an explanation; it is discussed in Chapter
Technical description: Binary IO module
.
†Note: When the user wishes to inject the signal at the PLC connection point of the “BO1-
SOURCE (200B01 31200E11D at the IO#1 slot)”, the user should set the BO1-
SOURCE (200B01 31200E11D) for the setting [Signal] of the F1 key. Then, set Off
for the scheme switch [BO1_CPL]
The user can select either Toggle or Instant modes for the signal generation using scheme
switch [LOGIC], as shown in Table 5.6-4. Thus, the user can substitute “F1-SIGNAL (240001
310001737)” for the “FUNC-KEY1 SIGNAL (240001 310001730)”, provided the Toggle mode
is preferred. In the Table 5.6-7 the other FUNC-KEY2 to FUNC-KEY7 are shown.
Table 5.6-4 Signal mode selection using setting [LOGIC]
Generated signal corresponding to pressing the function key
(iii) Lighting LEDs on F1 to F7
Figure 5.6-4 shows the F1 to F7 LED logics. Programing to light the LEDs (F1 to F7) is the
same as the programing of the LED indicators (#3 to #26) (for the programming, see section
5.6.2). As a default, e.g., the “FUNC-KEY1 (240001 310001730)” is set for the setting [Input
signal 1] of the F1 LED logic. The LED-F2 to F7 points are listed in Table 5.6-8.